VR6 Votlage Regulator
Input
Voltage, rated 120 V
Voltage, limits 90-140 V
Frequency 50-240 Hz
Burden (at rated V) 1440 VA
Output
Voltage, continuous 65 Vdc
Voltage, forcing 10 sec. 100 Vdc
Current, continuous 12 Adc
Current, forcing 10 sec. 25 Adc
Min. feld resistance 4 Ohms
Sensing: 100 to 120 V +/-10% with standard 10K Ohm control, 1 phase or 3 phase, 50/60 or 400 Hz; 1 VA maximum burden per terminal
Paralleling: 1 A or 5 A for 6% droop maximum; 10 VA maximum burden; isolated for use in either reactive droop or cross-current method
Regulation accuracy: +/- 0.5% maximum over full range of generator loading and +/- 5% frequency variation
Under frequency protection breakpoints: Adjustable 45 to 65 Hz (50/60 Hz regulators only)
Regulator response: Less than 4 milliseconds
Thermal stability: Less than 0.5% per 40° ambient temperature change
Operating and storage temperature: - 40° C to + 70° C
Vibration: 0.5 G at 18 to 2000 Hz
Power dissipation: Less than 50 W at maximum continuous rating
Shock: Tested to withstand up to 20 Gs in each axis
Dimensions in inches (mm): 6.39 (162) x 8.38 (213) x 3.0 (76)
Net Weight: 2.5 lb (1.1 kg)