HZRC2000 Electric Clip-on grounding resistance meter
USD $100 - $529 /Piece
Min.Order:1 Piece
Huazheng Electric Manufacturing (Baoding) Co., Ltd.
Clip-on grounding resistance meter
Clip-on grounding resistance meter introduction:
clamp earth resistance meter is widely used in electric power, telecommunications, meteorology, oil, construction and industrial electrical equipment such as grounding resistance measurement, loop resistance measurement. When measuring circuit grounding system, without disconnecting ground deflectors, without auxiliary electrode, safe and fast. clamp earth resistance meter can measure ground fault can not be measured by traditional methods, can be applied to traditional methods can not measure the occasion,Clamp Ground Resistance value measured is a comprehensive grounding resistance and grounding lead resistance.
Clip-on grounding resistance meter specifications
Function | Ground resistance test, Loop resistance test |
Power Supply | 6VDC 4 PCS of AA Alkaline batteries |
Resistance Range | 0.01-1200Ω |
Resistance Resolution | 0.001Ω |
Highest Resistance Accuracy | ±1%±0.01Ω |
Data memory | 99 Sets |
Alarm Threshold Setting Range | Resistance: 1-199Ω |
Alarm Sound and Light | “Beep-beep-beep” alarm tone, Alarm Symbol Flashing, Press AL key to turn on, turn off Alarm or set Alarm Threshold. |
Interference Signal Recognition |
“Beep-beep-beep” tone, NOISE symbol blinking |
Working Temperature and Humidity | -20℃-55℃;20%RH-90%RH |
LCD Screen | 4 Digits LCD display, Screen L*W: 47mm*28.5mm |
Clamp Size | 65mm*32mm |
Clamp Opening Extent | 32mm |
Tester Weight | 1160g (With batteries) |
Clamp Dimension | L*W*T: 285mm*85mm*56mm |
Protection Level | Dual Insulation |
Structural Feature | Clamp CT |
Shifting | Automatic shifting |
External magnetic field | <40A/m |
External electrical field | <1V/m |
Single measurement time | 0.5 second |
Resistance measurement frequency | >1KHz |
Measured current frequency | 50/60Hz Automatic measurement |
Low Battery Indication | Low battery symbol displays when battery is lower then 5.3V |
Memory Full Indication | MEM symbol blinks when all 99 sets memory is full |
Over Range Indication | Out of range indication “OLΩ”, “L0.01” or “OL A” |
Auto Power-off | 5 minutes after Boot up |
Power Consumption | Max 50mA either in booting up or normally working, Continuously working for 30 hours |
RS232 Interface (Optional) | The data stored in the meter are uploaded to the computer through RS232 interface and data wire, Then generate report files |
Safety Provisions | IEC1010-1, IEC1010-2-032, Pollution level 2, CAT Ⅲ(600V) |
Accessories | Meter: 1 piece, Test ring: 1 Piece, Meter Suitcase: 1 Piece |
Huazheng Electric Manufacturing (Baoding) Co.,Ltd
Add: Room 510,Unit2,Chaoyanglong Building B, 1178 chaoyang North Street,Baoding Hebei China | |
Sales manager | Tina Zhu |
phone | (+86)312 3372757-805 |
Fax | (+86)312 3339602 |
Skype | tinazhu86 |
Trading company | Hebei Huanhai Export & Import Trading company |