MNS low voltage power distribution cabinet
Negotiable /Set
Min.Order:1 Set
Hubei Zhongsheng Electric Co., Ltd.
Product name | MNS low voltage power distribution cabinet | |||
Technical Data | ||||
Rated voltages | Rated operating voltage | 400V / 690V | Rated impulse withstand voltage | 6KV / 10KV |
Rated insulation voltage | 690V / 1140V | Rated frequency | 50Hz, 60Hz | |
Rated currrent | Copper busbars | Copper distribution bars | ||
Rated current | up to 6300A | Rated current | up to 2000A | |
Rated peak withstand current | up to 250KA | Rated peak withstand current | up to 176KA | |
Rated short-time withstand current | up to 100KA | Rated short-time withstand current | up to 100KA | |
Mechanical characteristics | Height | 2200mm | ||
Width | 400, 600, 800, 1000, 1200mm | |||
Depth | 600, 800, 1000mm | |||
Degrees of protection | According to IEC 60529 | |||
Functional compartments and segregation | ||||
The assembly is divided into compartments thus separating different functional areas. | ||||
Mechanical Design | ||||
1. Frame construction: The basic elements of the MNS frame construction are "C" shaped steel profiles with a 25mm hole pitch according to DIN 43660. This 25mm equals the dimension of 1E used in MNS to define the area usage with the switchgear. | ||||
2. Enclosure: MNS swithgear enclosure is made of sheet steel protected by galvanic coating and powder coating for maximum durability. | ||||
Features | ||||
1. It's design is verified in accordance with IEC 61439-1/2. | ||||
2. Optimum protection for personnel and plant. | ||||
3. Design verified by testing (type-tested) including arc fault containment. | ||||
4. High operational reliability and availability. | ||||
5. Earthquake-, vibration-, and shock-proof designs and available. | ||||
6. Maintenance-free busbar and frame construction. | ||||
7. Simple retrofitting procedures. | ||||
8. Compact, space-saving design. | ||||
9. Simplified project implementation utilizing Zhongsheng's dedicated engineering tools. | ||||
Environmental conditions | ||||
1. Ambient temperature: -10℃ ~ +40℃. | ||||
2. Relative humidity: < 85%, no condensation. | ||||
3. Altitude: 2000m and below. | ||||
4. Installation location: Vertical inclination is not more than 5 degrees, no fire and explosive danger, no conductive dust, corrosive gas and violent vibration. | ||||
Application | ||||
1. Infrastructure requirrments: Data centers. Airports. Office buildings. Shopping centers. Hospitals. Rail. | ||||
2. Industries: Oil & gas, on and off shore. Chemical/petrochemical. Pharmaceutical. Power stations. Paper. Water treatment. Mining. Steel. Food. Marine. |