programmable power analyzerr GH96-E4/C
Negotiable /Set
Min.Order:1 Set
Hangzhou Yasian Technology Co., Ltd.
Network multi-function electric instrument is a multi-function electric instrument with programmable measurement,
display, digital communication and electric energy pulse transmitting output etc., which can complete electrical
measurement,electric energy measurement, data display, acquisition and transmission, and can be widely applied
to substation automation, distribution automation, intelligent building, electric energy measurement, management
and evaluation within the enterprise. Measurement accuracy is 0.5 grade, which can realize LED site display and
remote RS-485 digital communication interface, and adopt MODBUS-RTU communication protocol.
Appearance Code | Name | Measurement | Display | Standard Function | Optional Function (combinable) | |
96 square | Network multi-function electric instrument | Three phase: U, I, P, Q, EP+, EP-, EQ+, EQ-, S, F, PF or some parameters | LED display | RS485 communication, electric energy pulse output |
4DI, 4DO, 4AO, each single phase harmonic, voltage, current unbalance factor. | |
80 square | ||||||
72 square | ||||||
2DI, 2DO, 2AO, single phase harmonic, voltage and current unbalance factor. |
Performance | Parameters | ||
Input Measurement Display | Voltage | Network | Three phase three-wire, three phase four-wire |
Rated value | AC 100V / AC 220V / AC 380V | ||
Overload | 1.2 times rated value (continuous); 2 times rated value/1s | ||
Power | <0.4VA (per phase) | ||
Impedance | >500kΩ | ||
Accuracy | RMS measurement, accuracy grade is 0.5 | ||
Current | Rated value | AC 1A/5A (or use diverter) | |
Overload | 1.2 times rated value (continuous); 10 times rated value/1s | ||
Power | <0.2VA (per phase) | ||
Impedance | <2mΩ | ||
Accuracy | RMS measurement, accuracy grade is 0.5 | ||
Frequency | 45~65Hz | ||
Power | Apparent power, active power accuracy is 0.5 grade, and reactive power accuracy is 1.0 grade | ||
Electric energy | Four-quadrant metering, active power accuracy is 0.5 grade, and reactive power accuracy is 1.0 grade | ||
Display | Programmable, switch-over, recycling (LCD) display | ||
Power | Working range | AC/DC85~270V | |
Power consumption | ≤5VA | ||
Output | Digital interface | RS485 interface, Modbus-RTU protocol | |
Pulse output | 2-way electric energy pulse output, pulse constant: 5000imp/KWh | ||
Environment | Working environment | -10~55°C | |
Storage environment | -20~75°C | ||
Safety | Withstand voltage | Input/power supply >2kV/1min, input/output >2kV/1min, power supply/output >1.5kV/1min(50Hz) | |
Insulation | Input, output, power supply to case >100MΩ | ||
Electric energy measurement range | Electrical degree of measurement range for active power and reactive power is 0~999999Mwh, electrical degree exceeding the value shall be counted from 0. |
(Subject to physical wiring diagram)
72 square (overall dimension: 72*72*69.5 mm Hole size:67*67mm)