BS 6622 standard 15kV medium voltage aluminum cable 240mm2
BS 6622 standard 15kV medium voltage aluminum cable 240mm2
BS 6622 standard 15kV medium voltage aluminum cable 240mm2
BS 6622 standard 15kV medium voltage aluminum cable 240mm2

BS 6622 standard 15kV medium voltage aluminum cable 240mm2

USD $1.78 - $45.55 /Meter

Min.Order:100 Meters

Supply Ability:
50 Kilometer / Kilometers per Month
Port:
Qingdao Tianjin
Payment Terms:
T/T Credit Card

Quick Details View All >

Place of Origin:
Hebei, China
Brand Name:
Wanfang
Model Number:
YJLV, YJLV22, YJLV32
Insulation Material:
XLPE
Type:
Medium Voltage
Application:
Construction

Hebei Wanfang Wire & Cable Group Co., Ltd.

Business Type: Manufacturer,Trading Company
Xingtai Hebei China
Main Products: Wires and Cables

Product Details

BS 6622 standard 15kV medium voltage aluminum cable 240mm2

 

Product Description

 

Production Process:

 

BS 6622 standard 15kV medium voltage aluminum cable 240mm2

 

 

Application
The single core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 3.8/6.6KV to 19/33KV and frequency 50Hz. They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.

Standards
BS 6622
BS 7835 (LSZH)

Construction

Conductor
Plain annealed copper or aluminium complying with IEC 60228/BS 6360. Copper conductors shall be stranded (class 2) and aluminium conductors shall be either solid or stranded (class 2).
Conductor Screen
Extruded layer of semi-conducting cross-linkable compound is applied over the conductor and shall cover the surface completely. The minimum thickness is 0.3mm and the maximum resistivity shall not exceed 500 Ohm-m at 90°C.
Insulation
Insulation is of cross-linked polyethylene compound XLPE (GP8) conforming to BS 7655-1.3 or EPR (GP7), conforming to BS 7655-1.2.

Insulaton Screen
Extruded layer of semi-conducting cross-linkable compound is applied over the insulation. The extruded semi-conducting layer shall consist of bonded or cold strippable semi-conducting compound capable of removal for jointing or terminating. As an option, a semi- conducting tape may be applied over the extruded semi-conducting layer as a bedding for the metallic layer. The minimum thickness is 0.3 mm and the maximum resistivity is 500 Ohm-m at 90°C. The screen is tightly fitted to the insulation to exclude all air voids and can be easily hand stripped on site.
Metallic Layer
The metallic layer shall consist of either copper tapes or a concentric layer of copper wires or a combination of tapes and wires. The metallic layer provides an earth fault current path, capable of withstanding fault current to earth of 1000A for one second at maximum temperature 160°C. Copper wires are applied over the conducting water blocking layer with a minimum diameter of 0.5mm. And over the copper wires, copper tape with minimum thickness of 0.1mm can be applied helically with overlap

Separation Sheath (for armoured cable)
The separation sheath comprises a layer of extruded PVC, PE or LSZH. The nominal thickness is calculated by 0.02Du + 0.6mm where Du is the fictitious diameter under the sheath in mm. The nominal separation sheath thickness shall not be less than 1.2mm.
Armour (for armoured cable)
The armour consists of round aluminium wire

Over Sheath
Overall sheath comprises a layer of extruded either PVC type 9 conforming to BS 7665-4.2 or MDPE type TS2 conforming to BS 7655-10.1. LSZH can be offered as an option. The oversheath is normally black in colour. When a DC voltage test is to be performed on the oversheath, a semi-conducting layer such as graphite coating shall be applied over the surface of the extruded oversheath. The nominal oversheath thickness is calculated by 0.035+D where D is the diameter immediately under the oversheath in mm. For cables with the oversheath not applied over the armour, the nominal oversheath thickness shall not be less than 1.4mm. And for cables with oversheath applied over the armour, the nominal oversheath thickness shall not be less than 1.8mm.

 

 

Physical Properties
Operating Temperature: up to 90°C
Temperature Range: -5°C ( PVC sheath ); -20°C ( PE sheath )
Short Circuit Temperature: 250°C (short circuit duration up to 5 seconds)
Bending Radius: 12 x OD

 

 

Current Rating Conditions:

Ground Temperature:20°C
Ambient Temperature (air):
30°C
Depth of Soil: 0.8m
Thermal Resistance of Soil: 1.5K•m/W

 

 

Three Core 8.7/15KV (Um=17.5KV)
Dimensional Data

Nom.
Cross-
Section
Area

 

Unarmoured Cables

Steel Wire Armoured Cables

Nom.
Insulation Thickness

Copper Wire Screen Area

Nom.
Sheath

Thickness

Approx. Overall Diameter

Approx. Weight

Copper Tape Screen Area

Nom.
Bedding

Thickness

Nom. Armour Wire Diameter

Nom.
Sheath Thickness

Approx. Overall Diameter

Approx.
Weight

CU

AL

CU

AL

mm2

mm

mm2

mm

mm

kg/km

mm2

mm

mm

mm

mm

kg / km

25

4.5

16

2.4

48.4

3000

2420

4.4

1.4

2.5

2.6

55.2

5600

5100

35

4.5

16

2.5

50.4

3450

2670

4.7

1.4

2.5

2.7

57.6

6130

5440

50

4.5

16

2.6

53.7

4140

3190

4.9

1.5

2.5

2.8

61.1

7010

6060

70

4.5

16

2.7

57.2

4980

3640

5.3

1.5

2.5

2.9

64.6

8030

6700

95

4.5

16

2.8

60.6

5900

4050

5.7

1.6

2.5

3.0

68.2

9160

7330

120

4.5

16

2.9

63.9

6870

4560

6.1

1.7

2.5

3.1

71.7

10340

8030

150

4.5

25

3.0

67.9

8030

5230

6.4

1.7

2.5

3.2

75.4

11730

8930

185

4.5

25

3.1

71.1

9310

5770

6.8

1.8

3.15

3.4

80.6

14170

10570

240

4.5

25

3.3

76.9

11390

6680

7.4

1.9

3.15

3.6

86.6

16670

11810

300

4.5

25

3.5

81.6

13510

7790

7.9

2.0

3.15

3.7

91.3

19140

13340

400

4.5

35

3.7

89.9

17130

9340

8.5

2.1

3.15

4.0

100.0

23360

15410

 

 

 

For more details,  pls contact us,  will reply you in 12 hours.

Packaging & Shipping

 Package:  steel drum,  or do as customer required

 

Delivery time:  within 10 workind days after got the down payment,  depends on the quantity

 

Shipment:  By sea,  by air, by road, by rail

 

Port of loading:  Tianjin,  Qingdao

 

BS 6622 standard 15kV medium voltage aluminum cable 240mm2

 

 

 

Our Services

 Prompt reply & instant communication available

 

Shared Freight for sample delivery

 

Photoes all-the-way for cargo tracing after order

 

Factory-visiting or Third-party inspection before shipment is welcomes

 

We also provide OEM service

 

 

 

Company Information

 ISO 9001:2008 & ISO 14001:2004 & OHSAS 18001:2007 certificated

 

Verified by Alibaba & TUV

 

Experienced Foreigh-trade team

 

Total solution for wires & cables

 

 

 

ANY OTHER QUESTIONS, PLS FEEL FREE TO CONTACT US.

 

 

 

Cathy Li

wfcablesale1  AT  wfcable  DOT  com

Tel:  86-0319-5460022

Fax:  86-0319-5460677

Whatsapp: +86-150 3097 2080

Skype:  sdchem001

QQ:  771395729

Website:  
               wanfangcable.en.china.cn

 

Contact Supplier

Address
Yaotai Village, Jiajiakou Township, Ningjin County

You May Like

New Products

Recommended Products

View More View Less

Find Similar Products By Category

Electrical Equipment & Supplies > Wires, Cables & Cable Assemblies > Electric Cable
Categories
Hi~