HFC-200 filling machine
USD $4,500 - $6,000 /Unit
Min.Order:1 Unit
Yantai Kaiyuan Metals And Machinery Co., Ltd.
DesignFeatures
HFC-200 filling machine
Descripion andSpecification
What is the traditional Filling Machine
by the pressure Difference to filling gas from big vessel to fm 200 cylinder
THe shortcoming is too much lose , the gas are too expensive , save the money to avoid gas losing
Use new machine
Application :This filling Mahine be used for HFC-227ea Fire suppression system cylinder gas Filling
Big Advantage : No need power , filling by Pressure balance
Suitable filling Gas : clean agent HFC-227ea Gas ,HFC-236fa ,
Advantage : filling both FM200 gas and Nitrogen , there are two inlet for filling nitrogen
can improve the efficiency of filling and reduce the lose of medicament.
Procedure guide-line for refilling (HFC-227ea) cylinder
Purpose:
To guarantee high quality (HFC-227ea) for your process
Start condition:
-Full (HFC-227ea) cylinder on your refilling spot.
-For your process suitable (HFC-227ea) quality confirmed in the COA (certificate of analysis) provided by Waysmos.
Safety requirements:
See MSDS (material safety data sheet)
Facilities required:
-Weight-bridge (or other indication on amounts)
-Double skin flexible hose with outside wire –twisted reinforcement
-Pump (centrifugal or vane pump)
Procedure steps:
1. Check COA of this (HFC-227ea) cylinder.
2. Check gross-weight of (HFC-227ea) cylinder.
3. Check two identical valves with PZ27.8 in good condition.
4. Place cylinder of (HFC-227ea) gas on flat floor in a position with the face formed by the two valves perpendicular to the floor. The upper valve will be the gas phase valve and lower one liquid phase.
5. Prevent the cylinder from rolling by blocking to the sides with bricks or woods or other proper materials.
6. Connect the gas phase valve of the cylinder to the gas phase valve of the target cylinder with a double skin flexible hose, likewise, the liquid phase valve to the liquid phase valve with pipes connected to a pump suitable for liquefied gas.
7. Open all the valves and allow the pump refill the liquefied gas into the target cylinder.
8. When expected quantity gas refilled into the target cylinder, close liquid phase valves immediately at first and then the gas phase valves.
9. Turn off the pump and disconnect the hose.
End of procedure.
The above is recommended. But also you can consider methods as follow.
1. Use nitrogen to press MH227® agent into the receiver. Please pay attention that for expediently refilling you need moderately heat up the supply cylinder by steam or chill the receiver by ice.
2. Put the supply cylinder on the higher site and let the receiver vacuum, then connect two cylinders. The gravity will let MH227® agent into the receiver.
APPLICATION
• Filling HFC-227EA cYLINDER
• Marine fire fighting
ProducPicures
Packing Picture
Strong Wooden Cartons But free Fumigation
Related Products Recommend
Automatic powder filling machine
N2 Filling machine
CO2 Filling machine
Fire extinguisher airtight test box
Fire extinguisher check device
Workshop Picture
Our Company Instruction
Product Approval
2015 EXHIBITION
Jan.19-21,2015 Booth No 1-G24,Hall 1, 2015 Intersec, Dubai, UAE
How to Contact US
If you are intersted in our HFC-200EA fire extinguisher, you can contact with us.
Send us inquiry if you have ALIBABA ID
If not, you can contact with us by e-mail or phone directly !!! 24 hours online service