Application range 

 

1. DZ47LE-100 residual current circuit breaker is suitable for frequency 50HZ,rated voltage unipolar two lines ,poles,three pole,three pole four lines ,four pole, 400V,rated current lines from 63A to 100A.

2. when the person get an electric shock or electric leakage current exceed the special value,residual current circuit breaker can be in a very short period of time quickly , to cut off the fault  power , to protect the safety of person and the electricity equipment ,at the same time can protect circuit and motor overload or short circuit ,a line is not frequent transformation and also the not frequent starting of the motor.

3. products comply with GB14048.2 and IEC60947-2 standard .

 

 

Main Technical Parameter

 

TypeNCLE-100
Pole1P+N, 2P3P, 3P+N, 4P
Rated current (A)63,80,100
Rated voltage(V)230400
Rated short circuit breaking capacity Icn(KA)6
Rated residual making/breaking capacity Im(A)2000
Rated residual action current In(A)0.03,0.1,0.3
Rated residual non-action current Ino(A)0.5In

 

Applicable conducting wire

 

Rated current(A)6380100
Nominal cross section of wire mm2162535

 

Residual current breaking time

 

In(A)In(A)Breaking time(s) when equals to rating following
In2In5In5,10,20,50,100,200,500a(A)Itb
6-630.03, 0.05, 0.1, 0.30.10.060.040.040.04

 

The over-current protection property

 

Ambient TemperatureInitial StatusTest CurrentExpected ResultExpected ResultNote
40±2oCCold position1.05In(In≤63A)t≤1hNon-release-
Cold position1.05In (In[63A)t≤2hNon-release-
Carried out immedi-ately after previous test1.30In(In≤63A)t < 1hReleaseCurrent smoothlyrises to specified value within 5s
1.30In (In>63A)t< 2hRelease
-5~+40oCCold position8.00Int≤0.2sNon-release-
Cold position12.00Int < 0.2sNon-release-

 rcbo breaker 30ma earth leakage breaker 30ma rcdrcbo breaker 30ma earth leakage breaker 30ma rcdrcbo breaker 30ma earth leakage breaker 30ma rcdrcbo breaker 30ma earth leakage breaker 30ma rcdrcbo breaker 30ma earth leakage breaker 30ma rcd

 

 

Contact Supplier

Ms. Alisa Wen Manager Chat Now
Telephone
86-577-6178113713968753226
Mobile
13968753226
Fax
86-577-61615776
Address
Xiangyang Industry Park, Liushi Town, Yueqing City Wenzhou,Zhejiang

You May Like

New Products

Recommended Products

View More View Less

Find Similar Products By Category

Electrical Equipment & Supplies > Circuit Breakers
Categories
Hi~