LYNX ACSR from New Baofeng
USD $1 - $500 /Meter
Min.Order:500 Meters
Hebei New Baofeng Wire & Cable Co., Ltd.
ACSR
Type of conductor:
1 AAC:All Aluminium Conductors
ASC:Aluminium Stranded Conductors
2 AAAC:All Aluminium Alloy Conductors
AASC:Aliminium Alloy Stranded Conductors
3 ACSR:Aluminium Conductor Steel Reinforced
ACSR Technical Characteristics Based on Standard BS 215-2
Code name | Nominal aluminium area | Stranding and wire diameter | Sectional area of aluminium | Total sectional area | Approx. overall diameter | Approx. mass | Calculated D.C. resistance at 20oC | Calculated breaking load | |
Al | Steel | ||||||||
mm2 | No./mm | mm2 | mm2 | mm | kg/km | Ω/km | kN | ||
RABBIT | 50 | 6/3.35 | 1/3.35 | 52.88 | 61.7 | 10.05 | 214 | 0.5426 | 18.35 |
DOG | 100 | 6/4.72 | 7/1.57 | 105 | 118.5 | 14.15 | 394 | 0.2733 | 32.7 |
WOLF | 150 | 30/2.59 | 7/2.59 | 158.1 | 194.9 | 18.13 | 726 | 0.1828 | 69.2 |
DINGO | 150 | 18/3.35 | 1/3.35 | 158.7 | 167.5 | 16.75 | 506 | 0.1815 | 35.7 |
LYNX | 175 | 30/2.79 | 7/2.79 | 183.4 | 226.2 | 19.53 | 842 | 0.1576 | 79.8 |
ZEBRA | 400 | 54/3.18 | 7/3.18 | 428.9 | 484.5 | 28.62 | 1621 | 0.0674 | 131.9 |
AAAC Technical Characteristics Based on Standard BS 3242
Code name | Nominal aluminium area | Stranding and wire diameter | Sectional area | Approx. overall diameter | Approx. mass | Calculated D.C. resistance at 20oC | Calculated breaking load |
mm2 | No./mm | mm2 | mm | kg/km | Ω/km | kN | |
ALMOND | 25 | 7/2.34 | 30.1 | 7.02 | 82 | 1.094 | 8.44 |
CEDAR | 30 | 7/2.54 | 35.47 | 7.62 | 97 | 0.9281 | 9.94 |
FIR | 40 | 7/2.95 | 47.84 | 8.85 | 131 | 0.688 | 13.4 |
HAZEL | 50 | 7/3.30 | 59.87 | 9.9 | 164 | 0.5498 | 16.8 |
OAK | 100 | 7/4.65 | 118.9 | 13.95 | 325 | 0.2769 | 33.3 |
ASH | 150 | 19/3.48 | 180.7 | 17.4 | 497 | 0.183 | 50.65 |
ELM | 175 | 19/3.76 | 211 | 18.8 | 580 | 0.1568 | 59.1 |
UPAS | 300 | 37/3.53 | 362.1 | 24.71 | 997 | 0.09155 | 101.5 |