medium voltage wire/fire resistant electric wire/fire proof cable/fire alarm wire
USD $0.6 - $5 /Meter
Min.Order:1000 Meters
Hebei New Baofeng Wire & Cable Co., Ltd.
medium voltage wire/fire resistant electric wire/fire proof electric wire/fire alarm wire
low voltage wire/fire resistant electric wire/fire proof cable/fire alarm wire
low voltage wire/fire resistant electric wire/fire proof electric wire/fire alarm wire
No Halogen Flame Retardant cable and Fire resisant power cable
Fire resistant electric wire, Fire proof electric wire, Fire alarm electic wire ,XLPE/PVC insulated, Copper/Aluminum conductor ,low voltage, medium voltage
Product standard
The electric property of the product is the same as those common wire and cable, and its properties of fire-resisting conform to the GB/T18380-2001(IEC60332:1993) and GB/T19216.21-2003 the State Standard or the GA306-2007 the Public Safety Industrial Standard regulated by the State.
Usage
This product is suitable for use in all places using rated AC voltage 1-10kV plastic insulated power cable, 450/750V plastic insulated control cable, 450/750V and below electrical equipment wire and cable, particularly high temperature, inflammable and fire-proof for transmitting and distributing power, control, alarm fire-control system and other circuits.
Property for Use
1. According to different product kinds, rated voltage can be divided into the following:
a,0.6/1-8.7/10kV b,450/750V c,300/500V d,300/300V
2. Allowed work temperature of cable for a long period is divided into the following according to different kinds of products: 70°C, 90°C, 105°C.
3. For short circuit (5s), the allowed max. work temperature of conductor does not exceed 160°C and 250°C (for 1-a).
4. Environmental temperature for laying cable should not be less than 0°C.
5. Allowed min. bend radius of cable should be according to different kinds of the following products: 6 times, 10 times, 12 times and 15 times of cable overall diameter.
6. Cable combustion nature
a. Under flame temperature 750-800°C combustion conditions, cable can normally operate not less than 90 min.
b. Measured cable current-carrying capacity under “a” environment is not less than the current-carrying capacity
value under work conditions of less than the current-carrying capacity value under work conditions of corresponding type and specifications of common cable.
7. Other electric nature and physical-mechanic nature of cable are all higher than corresponding cable.
Diagram of structure