12KW 48V DC Gasoline generator for Telecom Shelters/Telecom Tower
USD $4,400 - $4,999 /Unit
Min.Order:1 Unit
Chongqing Zhiren Electric Equipment Co., Ltd.
48 V DC generator for Telecom Shelters
1. Permanent magnet 48V DC generator for emergency power in Telecom BTS.
2. Small size, light weight, stable performance, low failure rate;
3. Energy-saving and low emission; low fuel consumption;
4. Module design, safe and reliable; with alarm functions of over voltage, short circuilt, overheat power supply module, engine oil alert;
5. can work separately as well as work together in cabinets to supply power for telecom equipments.
6. 50A/100A 5kw 48v dc generator is ease of operation and maintainenance,
Protection characteristics
battery reverse connection protection,timing shutdown protection,
grid supply stop engine protection (optional),
engine preheating protection;
engine lubricating oil level alarm protection,
over-voltage protection,
over-current protection,
limit-current protection,
short-circuit protection,
module over-heating protection
Technical Parameter
Model | YH12000M48-200 | ||
Generator | Excitation System | Rare-earth Permanent Magnet | |
DC output Voltage(V) | 48V (Rated voltage) (40V-59V continuous adjustable) 48V (rating voltage) 53.5V(floating voltage) 56.4V(Equalized Charging ) | ||
DC output Current(A) | 100A (Rated current ) (2A-110A continuous adjustable) 100A(Equalized Charging) 110A (rating voltage) 105A (floating voltage) | ||
DC output Power [kw/(r/min)] | 12/3600 | ||
Power (kW) | DC12KW, AC230/6KW, AC400/12KW | ||
Engine | Brand | Briggs &Stratton 3854, 21HP | |
Type | OHV,AIR COOLED, 4 STROKE | ||
Displacement(cm³) | 627 | ||
Continuous Power [kw/(r/min)] | 12/3600 | ||
Start | electric start/hand recoil start | ||
Lubricating | Lubricating oil type | ||
SJ 10W-30 (API grade SE or above) | |||
Lubricating oil capacity(L) | 1.1 | ||
Fuel | car use unleaded gasoline (90# or above) | ||
Protection | Fule consumption(g/kw.hr) | ≤220 | |
Environmental characteristics | 70kPa~106kPa (plateau equipped with special carburator) | ||
-40℃~+55℃ | |||
-55℃~+70℃ | |||
Protection characteristics | battery reverse connection protection, timing shutdown protection, grid supply auto-shutdown protection (optional), engine preheating protection; engine lubricating oil level alarm protection, over-voltage protection, over-current protection, limit-current protection, short-circuit protection, module over-heating protection | ||
Fuel tank capacity(L) | 14/100 | ||
Start condition (stationary automatic type ) | Grid supply unavailable; -48V batteries for voltage lower limit; | ||
Shutdown condition(stationary automatic type ) | Grid supply available; | ||
-48V batteries voltage upper limit voltage; batteries charging current ; Timing shutdown | |||
Continuous work tim(hour/ratedpower) | 4.5/32 | ||
Noise level [non-load~full-load[dB(A)] | 75~80 | ||
Dimensions(L×W×H) (mm) | 1102×712×957 | ||
Weight(net weight) | ≤158KG |