Installation of unit
1. The unit shall be installed by professional personnel.
2. The fan coil unit shall be handled with cares and protected from heavy compression. Handling the unit with hand holding the impeller or spiral case shall not be allowed.
3. Before installation, the unit shall be checked for damage. In case of collision damage, deformation or dropping of fan motor, please contact the dealer for repair or replacement.
4. For safety, the lifting apparatus for the unit shall be sufficiently strong to bear running weight and vibration. The unit is merely allowed to bear its own weight and shall not be stressed by air pipeline and water pipeline or other external objects. The unit shall be kept level, or the
5. condensed water would overflow.
Connection of pipeline and anti-frosting measures
1. The water inlet and outlet pipelines shall be connected carefully and the torque shall not exceed the specified value. It is recommended to seal the connections with sealing tape to avoid torsion-generated leakage.
2. The water inlet and outlet pipelines shall be thermally insulated to avoid generation of condensed water.
3. The condensed water pipeline shall have drain slope of at least 0.005 to facilitate draining of condensed water.