2 Channel Switch / proximity Detector relay
Negotiable /Piece
Min.Order:1 Piece
2 Channel Switch/ proximitly Detector Relay
Model: MTL 3013
Maker: MTL Instruments Ltd,
Um= 250 V
Max. Amb temp: 60°c
Number of Channels | Two, interconnected, fully floating |
Location of Switch | Zone 0, IIC, T6 hazardous area Div 1, Group A, hazardous location |
Location of proximity detector | Zone 0, IIC, T4–6 if suitably certified Div 1, Group A, hazardous location |
Voltage applied to sensor | 7.0 to 8.5V dc from 970Ω |
Input/ Output characteristics (each channel) | Output closed if >2.1mA* (<2kΩ) in sensor circuit |
Phase reverse Facility | Operations reversed by switches on top of unit |
Power supply failure protection | Output circuits open if supply fails |
Relay characteristics | Each single-pole on/off, open when relay de-energised Response time: 10ms typical |
LED indicators (each channel) | ON when output circuit is closed |
Power Requirement | 55mA typical at 24V 75mA maximum at 20 to 35V |
Power Dissipation | 1.4W typical at 24V 1.6W maximum at 35V |
repleacable fuse | 80mA, 5 x 20mm glass to DIN41571 sht 2, semi-time-lag (M) |
Safety description (each channel) | 10.5V, 800Ω, 14mA, Um = 250V rms or dc |
FM max entity parameters | Voc = 10.5V, Isc = 14mA, Ca = 2.4μF, La = 16 |
weight | 170g |