Endress + Hauser RN 221N Active Barrier
Negotiable /Piece
Min.Order:1 Piece
Active Barrier
Model: RN 221N
Maker: Endress + Hauser RN 221N
Input: 4...20 mA
Output: 4...20mA
Operation and System construction:
Measurement principle | Active barrier with power supply for safe separation of 4 to 20 mA current signal circuits. The unit has an intrinsically safe input. The current transmitted from the source to the input circuit (4 to 20 mA) is linearly transmitted to the output. |
Measurement System | The unit creates a safe galvanic isolation between input and output of the circuits for safe separation between hazardous and nonhazardous areas. A built-in loop power supply can supply connected sensors with the necessary energy. A current signal is available at the output (passive output) for connection to further instrumentation. Bi-directional HART® communication with SMART transmitters is possible using the built-in communication sockets (with resistance R = 250 Ω). |
Input:
Number of inputs | 1 |
Power requirement | 16.7V ± 0.2V (at I = 20 mA) |
Internal resistance | 328 Ω |
Over range | 10 % |
Output:
Open circuit voltage | 27.3 V |
Short circuit current | 87.6 mA |
Power Consumption | 597 mW |
Capacitance | 86 nF [EEx ia] IIC; FM IS CL. I, Div. 1, Grp. A, B |
Inductance | 5.2 mH [EEx ia] IIC; FM IS CL. I, Div. 1, Grp. A, B |
Number | 1 |
Open Circuit voltage | 24 V ± 10% |
Over range | 10% |
Load (impedance) | 0 to 700 Ω (without communication resistance) |
Galvanic isolation | To all other current circuits |