4 loops addressable fire alarm control panel
USD $837 - $842 /Set
Min.Order:1 Set
Products:
4 loops addressable fire alarm control panel
Main feature
1. More than 64 panels could be connected in one network.
2. One panel could connect 2 to 24 loops.
3. One loop could connect 198 addressable devices include the detectors and modules.
4. SLC(Single Loop Circuit) operated up to 10. 000 ft. (3, 800m) with twisted, unshield D.3.2mm² wire or 3,000ft(900m) with untwisted, unshield D1.0mm² wire.
5. Powerful polling protocol for faster panel response time less than 4 seconds, And response time less than 5 seconds from one panel to another panel in the network.
6. 320*240 Color TFT LCD display.
7. Software bases on ARM9 processor.
8. Devices(detectors and modules) could be registered automatically.
9. Each addressed devices could be have a name with up to 40 characters(including spaces).
10. More than 2000 cuases and effect items could be used to active output modules by alarm, fault, supervision, feedback in flexible and simple syntax.
11. History file with 5,000 events capacity.
12. Graphic PC monitor software can be connect to the panel by RS232 OR MODBUS port(optinal)
13. More than 500 users could be registered in different level and password.
14. The panel could be programmed by USB port to download or upload program data.
15. Fully programmable from local keypad or keyboard or local PC.
16. The detector real time sampling data curve could be showing on the LCD.
Technical specification:
AC Power – Terminal DZ1 of Main Circuit Board
220 VAC, 50 Hz, 1.5 amps
Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation
Battery (Sealed Lead Acid Only) – Terminal DZ2 of Main Circuit Board
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 1.00 amp
Maximum Battery Size: 18 Amp Hour
Minimum Battery Size: 7 Amp Hour
(FACP cabinet holds maximum of two 18 Amp Hour batteries. For greater
than 18 Amp Hour up to 26 Amp Hour batteries, use additional Battery Box)
Resettable DC24V Power (24 VDC nominal) –
Terminal DZ3, Terminals 1 (+) & 2 (-) & 3 (+) & 4 (-) of Main Circuit Board
Maximum ripple voltage: 10 mVRMS
Up to 1.5 amps is available for powering devices.
Power-limited circuit, nonsupervised
Nonresettable DC24V Power (24 VDC Nominal) –
Terminal DZ3, Terminals 5 (+) & 6 (-)
Maximum ripple voltage: 10mVRMS
Total DC current available from each output is up to 1.5 amps
Power-limited circuit, nonsupervised
Four Programmable Output Relay
Service:
1.Your inquiry can be respond in 12 hours by well trained and experienced staff in fluent English.
2.We can help you to design your customized products and put them into production.
3.Delievery by DHL,UPS,EMS or by sea as per your requirements.
4.The best quality,the lowest price,fast delievery.
Factory show:
Cetification: