AC variable resistive ac power dummy load for watt meter
Negotiable /Set
Min.Order:1 Set
Shaanxi Aitelong Technology Co., Ltd.
SAT-ACO380 AC load is AC variable resistive generator dummy load for 100kva power bank
Functions & Features
-Test discharge three-phase voltage, current, active power, reactive power, apparent power, power factor, frequency, running time, energies of generators and UPS.
-Set/adjust discharging power according to performance parameters and detection requirements
-Set discharging time, timing to automatic shut-off load, discharge off and alarm operator
-Set over/under voltage protection threshold value, it can shut off load, terminate discharging and alarm user automatically.
-Large LCD screen, friendly interface. English menu and easy operation.
-Parallel operation function to carry out multi sets load operation by RS 485 communication
-Built-in storage function, save 30 groups of test data, which can be inquired, deleted and put into SD card.
-Start/stop discharging control by Serial port, and detect data real time operation etc; The storage data can be uploaded to PC by serial port or SD card, and the upper computer’s software can analyze data and pattern and print report etc.
-Overheating and over current protection function, it can turn off load, terminate discharging and alarm automatically when over temperature and over current.
-Set at most 5 groups power, load process automatically according to the setting power and operation time after being turned on.
Mode | ACO 380/02 | ACO 380/04 | ACO 380/10 | |||
Working environment | Working Temperature: (-20~55)℃ Storage Temperature: (-45~75)℃ Relative humidity: 90%(40±2℃) Atmospheric pressure: (70~106)KPa | |||||
Working power supply | Single-phase AC220V±10, 50Hz | |||||
Load voltage | Three-phase AC380V, Single-phase AC220V | |||||
Operating power | Stand-alone: Max 20KW (Three-phase 380V) Max 6KW (Singly-phase 220V) | Stand-alone: Max 40KW (Three-phase 380V) Max 13KW (Singly-phase 220V) | Stand-alone: Max 100KW (Three-phase 380V) Max 30KW (Singly-phase 220V) | |||
Cooling mode | FCT(Fan control Temperature) | |||||
Communication Mode | RS232, RS485 and SD card | |||||
Display mode | 8 inch TFT | |||||
Voltage measurement range | AC 0~450V, Display Resolution: 0.1V, Precision: ±0.5% | |||||
Current measurement range | AC 0~100A, Display Resolution: 0.1A, Precision: ±0.5% | AC 0~150A, Display Resolution: 0.1A, Precision: ±0.5% | AC 0~300A, Display Resolution: 0.1A, Precision: ±0.5% | |||
Frequency measurement range | 40~60 Hz, Display Resolution: 0.01Hz, Precision: ±0.2% | |||||
Power measurement range | 0~20 KVA, Display Resolution: 0.1KVA, Precision: ±1% | 0~40 KVA, Display Resolution: 0.1KVA, Precision: ±1% | 0~100 KVA, Display Resolution: 0.1KVA, Precision: ±1% | |||
Power factor measurement range | 0.001~1.000, Display Resolution: 0.001, Precision: ±0.5% | |||||
Discharging Time | (0~19 hours and 59 minutes) adjustable continuously | |||||
Quantity of Parallel operation | 1~99 sets | |||||
Recording Period | 6~999 Seconds | |||||
Temperature measurement range | -20~100℃,Display resolution: 1℃, precision:±1℃ | |||||
Insulating strength | Input≥AC1500V Output≥AC500V | |||||
MTTF | ≥50000h | |||||
Dimensions(mm) | 420×500×750mm | 680×600×900mm | 680×600×900mm | |||
Weight | 30kg | 50kg | 70kg |