BCC, Bare Copper Stranded Conductor (BS EN 13602)
USD $1 - $30 /Meter
Min.Order:500 Meters
AACSR, Aluminium Alloy Conductors Steel Reinforced (NF C 34-125)
AACSR, Aluminium Alloy Conductors Steel Reinforced (DIN 48206)
AACSR, Aluminium Alloy Conductors Steel Reinforced (ASTM B711)
AAC Conductor, overhead bare conducotr, All Aluminium Conductor (IEC 61089)
AAAC/AASC Conductor Power Cable All Aluminum Alloy Conductor (CAN/CSA CS 49.1)
BCC, Bare Copper Class 2 Conductor (BS EN 13602)
Applications
For use in electrical grounding systems and on insulators for overhead transmission and distribution applications. Stranded conductors offer greater flexibility than solid.
Cable Standards
BS EN 13602, BS EN 60228
Construction
Conductor
Class 2 annealed stranded copper conductor according to BS EN 60228 (previously BS 6360)
NOMINAL CROSS SECTIONAL AREA | NO. OF WIRES | DIAMETER OF WIRES | DIAMETER OF CONDUCTORS | Minimum Elongation | Minimum Tensile Strength | NOMINAL WEIGHT | MAXIMUM DC RESISTANCE AT 20°C |
mm2 | mm | mm | % | N/mm2 | kg/km | ohms/km | |
1.5 | 7 | 0.53 | 1.59 | 24 | 200 | 13 | 12.1 |
2.5 | 7 | 0.67 | 2.01 | 24 | 200 | 21 | 7.41 |
4 | 7 | 0.85 | 2.55 | 24 | 200 | 35 | 4.61 |
6 | 7 | 1.05 | 3.15 | 26 | 200 | 52 | 3.08 |
10 | 7 | 1.35 | 3.85 | 26 | 200 | 87 | 1.83 |
16 | 7 | 1.74 | 4.8 | 28 | 200 | 137 | 1.15 |
25 | 7 | 2.19 | 5.8 | 28 | 200 | 215 | 0.727 |
35 | 7 | 2.62 | 6.9 | 28 | 200 | 300 | 0.524 |
50 | 10 | 2.62 | 8.2 | 28 | 200 | 410 | 0.387 |
70 | 14 | 2.62 | 9.7 | 28 | 200 | 595 | 0.268 |
95 | 19 | 2.62 | 11.4 | 28 | 200 | 820 | 0.193 |
120 | 24 | 2.62 | 13.1 | 28 | 200 | 1040 | 0.153 |
150 | 30 | 2.62 | 14.2 | 28 | 200 | 1280 | 0.124 |
185 | 37 | 2.62 | 15.8 | 28 | 200 | 1600 | 0.0991 |
240 | 48 | 2.62 | 18.6 | 28 | 200 | 2100 | 0.0754 |
300 | 58 | 2.62 | 20.4 | 28 | 200 | 2700 | 0.0601 |
400 | 55 | 3 | 26 | 33 | 200 | 3400 | 0.047 |
500 | 70 | 3 | 30 | 33 | 200 | 4400 | 0.0366 |