Single drum threaded pipe coal fired hot water boiler
USD $45,000 - $50,000 /Set
Min.Order:1 Set
Qingdao Xingfu Boiler Thermoelectric Devices Co., Ltd.
Single drum threaded pipe coal fired hot water boiler
Single drum threaded pipe coal fired steam boiler
Single drum threaded pipe coal fired boiler
Model/Parameter/Item | DZL 2-0.7-AII | DZL 2-1.25-AII | DZL 4-1.25-AII | DZL 4-1.6-AII | DZL 6-1.25-AII | ||
Rated capacity | t/h | 2 | 2 | 4 | 4 | 6 | |
Operation pressure | Mpa | 0.7 | 1.25 | 1.25 | 1.6 | 1.25 | |
Steam temperature | C | 169.6 | 194 | 194 | 203 | 194 | |
Water-inlet temperature | C | 20 | 20 | 20 | 60 | 20 | |
Heating efficiency | % | 77.4 | 77.4 | 81 | 81 | 77.4 | |
Area of stoker | m2 | 3.04 | 3.2 | 5.4 | 5.4 | 7.48 | |
Steam valve diameter | mm | PN1.6 DN80 | PN1.6 DN80 | PN1.6 DN100 | PN2.5 DN100 | PN1.6 DN125 | |
Water inflow valve diameter | mm | PN1.6 DN40 | PN1.6 DN40 | PN1.6 DN50 | PN2.5 DN50 | PN1.6 DN50 | |
Fuel | Coal available |
| II type bitumite,lcv:17700-21000KJ/kg | ||||
Consumption | kg/h | 290 | 290 | 580 | 580 | 960 | |
Dimension of biggest parts for shipment (LxWxH) | m | 5.82*2.1*3.22 | 5.82*2.1*3.22 | 6.5*2.66*3.52 | 6.5*2.66*3.52 | 7.1*3*3.65 | |
Weight of biggest parts for shipment | t | 18 | 19 | 27 | 29 | 32 | |
Overall dimension of Assembled boiler (LxWxH) | m | 6.5*4.0*3.7 | 6.5*4.0*3.7 | 7.2*4.5*4.0 | 7.2*4.5*4.0 | 7.9*4.5*4.1 | |
Water supply | Model |
| 11/2GC-5*4 | 1 1/2GC-5*4 | 11/2GC-5*7 | 1 1/2GC-5*7 | 2GC-5*6 |
Motor power | kw | 3 | 7.5 | 7.5 | 11 | 15 | |
Blast fan | Model |
| G6-41-13No 5.4A | G6-41-13No 5.4A | G6-41-13No 6.4A | G6-41-13No 6.4A | G6-41-13No 7.1A |
Flow | m3/h | 4358-2310 | 4358-2310 | 7358-3596 | 7358-3596 | 10354-5349 | |
Pressure | Pa | 994-1254 | 994-1254 | 1436-1181 | 1436-1181 | 2270-1697 | |
Motor power | kw | 3 | 3 | 5.5 | 5.5 | 7.5 | |
ID fan | Model |
| Y6-41-13No 5.4C | Y6-41-13No 5.4C | Y6-41-13No 7.1C | Y6-41-13No 7.1C | Y6-41-13No 10C |
Flow | m3/h | 8901-4350 | 8901-4350 | 15219-8171 | 15219-8171 | 32144-16607 | |
Pressure | Pa | 2568-3240 | 2568-3240 | 2454-3283 | 2454-3283 | 2574-3444 | |
Motor power | kw | 11 | 11 | 22 | 22 | 37 |
Model/Parameter/Item | DZL1.4- 0.7-95/70-AII | DZL2.8- 0.7-95/70-AII | DZL4.2- 1.0-115/70-AII | ||
Rated capacity | MW | 1.4 | 2.8 | 4.2 | |
Operation pressure | Mpa | 0.7 | 0.7 | 1 | |
Hot water temp. | C | 95 | 95 | 115 | |
Water-inlet temperature | C | 70 | 70 | 70 | |
Heating efficiency | % | 76 | 76 | 78 | |
Area of stoker | m2 | 3.04 | 5.14 | 7.4 | |
Heating area | m2 | 12000 | 24000 | 36000 | |
Water inlet & outlet Diameter | mm | PN1.6 DN100 | PN1.6 DN125 | PN1.6 DN150 | |
Fuel | Coal available |
| II type bitumite,lcv:17700-21000KJ/kg | ||
Consumption | kg/h | 290 | 580 | 960 | |
Dimension of biggest parts for shipment (LxWxH) | m | 5.82*2.26*3.22 | 6.51*2.6*3.52 | 7.5*2.9*3.5 | |
Weight of biggest parts for shipment | t | 19.1 | 26.5 | 31 | |
Overall dimension of Assembled boiler (LxWxH) | m | 6.5*2.55*4.53 | 7.5*4.0*5 | 7.9*4.5*4.4 | |
Water pump | Model |
| IS80-65-160 | IS100-80-160 | IS125-100-200B |
Flow | m3/h | 50 | 100 | 172 | |
Lift | m | 32 | 38 | 37 | |
Motor power | kw | 7.5 | 15 | 30 | |
Blast fan | Model |
| G6-41-13No 5.4A | G6-41-13No 6.4A | G6-41-13No 7.1A |
Flow | m3/h | 4358-2310 | 7358-3596 | 10354-5349 | |
Pressure | Pa | 994-1254 | 1436-1181 | 2270-1697 | |
Motor power | kw | 3 | 5.5 | 7.5 | |
ID fan | Model |
| Y6-41-13No 5.4C | Y6-41-13No 7.1C | Y6-41-13No 10C |
Flow | m3/h | 8901-4350 | 15219-8171 | 32144-16607 | |
Pressure | Pa | 2568-3240 | 2454-3283 | 2574-3444 | |
Motor power | kw | 11 | 22 | 37 |