PCE-PA 8000 three-phase power analyzer
Negotiable
Min.Order:1
Technical specifications | ||
Voltage (AC V) | ||
Measurement range | Resolution | Accuracy |
10 V ... 600 V (phase to neutral) | 0.1 V | ±(0.5 % + 0.5 V) |
10 V ... 600 V (phase o neutral) | ||
Current (AC A) | ||
Measurement range | Resolution | Accuracy |
20 A | 0.001 A (<10 A) | ±(0.5 % + 0.1 V) |
200 A | 0.01 A (<100 A) | ±(0.5 % + 0.5 A) |
1200 A | 0.1 A (<1000 A) | ±(0.5 A + 5 A) |
General technical specifications | ||
Display | 3.7 " LCD (320 x 240 pixels) with LED backlight | |
Electrical properties | AC V, AC A, active power, apparent power, power factor, phase angle, mains frequency | |
Voltage ranges | 10 V ... 600 V AC, automatic range selection | |
Security / Standards | IEC1010CAT III 600V | |
AC V input resistance | 10 MΩ | |
Operation frequency of current clamps | 40 Hz ... 1 kHz | |
Tested operation frequency of current clamps | 45 Hz ... 65 Hz | |
Overload protection | AC V | 720 V rms |
AC A | 1300 A with currentclips | |
Memory | SD card | |
Measurement rate | 1 second | |
Data logger | SD | |
Measurement rate | 2 seconds... 7200 seconds | |
Data output | USB or RS-232, depending | |
Operating temperature | 0 ºC ... 50 ºC | |
Operating humidity | <80 % H.r. | |
Power | 8 x 1.5 V AA batteries / mains component | |
Input current | Meter: 300 mA DC | |
Max. diameter | 50 mm | |
Weight | Meter: 948 g (with batteries) | |
Dimensions | Meter: 225 x 125 x 64 mm | |
Clamp: 210 x 64 x 33 mm | ||
jaw: 86 mm (exterior) |