Magnetic Contactor switch cj19

Magnetic Contactor switch cj19

USD $4.9 - $20 /Unit

Min.Order:100 Units

Supply Ability:
10 Unit / Units per Month
Port:
Ningbo or Shanghai
Payment Terms:
T/T D/P D/A Credit Card

Quick Details View All >

Place of Origin:
Zhejiang, China
Brand Name:
Dixsen
Model Number:
CJ19
Electricity Type:
AC
Number of Pole:
3
Phase:
3

Zhejiang Dixsen Electrical Co., Ltd.

Business Type: Manufacturer,Trading Company
Wenzhou Zhejiang China
Main Products: Current Transformer ,Panel Meter ,AC Contactor ,Circuit Breaker ,Transformer

Product Details

Specifications

1. ISO9001 and ISO14001 approval.
2. CE passed.
3. Professional manufacturer.
4. Reasonable packing.

Magnetic Contactor switch cj19

Application

Contactors provide remote control of primarily electric motors and compensation & heating systems by cable. They protect the instruments and equipments against overload currents by using thermal relays, for Capacitor switching contactor: While switching on a capacitive circuit, a high frequency (1~15Hz) and large transient current peaks are produced. Switching of capacitor for a single or one of the capacitor banks are different from each other. Step by step switching on operation is more difficult for contactor than capacitor bank. Because during this operation for capacitor bank, compensated current occurs. For this reason selecting of suitable contactors the compensating current must be taken into consideration for 50KVAR and above, and for less than 50KVAR can be omitted. Dixsen offer complete range of contactors for most kinds of applications.

Why Capacitor switching contactor?

As it is known, when the capacitor starts to operate, they cause a high frequency between 1-15 kHz. And a current that is 180 time higher than rated current for very short time period. Shock inductance is to be fixed to each phase to limit this current. But practically this type of operation is difficult. That is why capacitor switching contactors are used and for this reason the ife-time of contactors increase 100% in comparision with normal contactor.

Magnetic Contactor switch cj19

Fulfill following Standard

IEC60947-4-1, EN60947-4-1

 

Contact material

Silver cadmium oxide

 

Contact

Main and auxiliary contact, coil and auxiliary contact blocks are easily installed and removed. The coils of contactors are safely controlled between 0.8 and 1.1 times of their rated coil voltage. They operate at full performance in the ambient temperature of -5 and +55. The ability of assembling contactors to rails provides a great facility during installation. The ingredient of the material provides a resistance to an insulation voltage of 1000V.

 

Contactors damages and repairs

Contactor damages and effects of these damages

There can be damages when the contactors are not used according to technical datas and then failures begin to occur at the feeding system. Reasons of probable cancellation of Contactors. Generally, contactors are the devices, which do not damage easily. If the selection is made correctly and operating conditions are not out of order, contactor can make millions times opening and closing safely. The reasons of the cancellation and their solutions are given below.


Excessive length of cable of command circuit (coil) can cause some problems. Voltage is low during the long cables and this reason makes the closing difficultly and over big cross-sectioned cable capacitance obstruct opening. Generally advised cable cross-selection and length are mentioned in catalogues. If the command circuit is longer than the advised value, higher contactor and more lower coil voltage, resistance or inductive impedance connection should be used.


Dirt or foreign particles in the contactor, hard atmosphere conditions and corrosion can obstruct the closing operation of contactor. If we face a problem like this, contactor should be cleaned, appropriately. Then the circuit should be checked and modified for a more protective environment for the contactor. If there is a factor damaging the conduction, it should be removed.


Events that can cause the contactors, noisy operation is dust and having foreign particles in the air space etc, unsuitable voltage and frequency. Also defect of the nucleus surface because of long time operation. To obstruct all these, we should provide the clearness of the nucleus face and (if needed) coil changing should be made for voltage and frequency.

 

Changing the coil

New coil is put on by pulling up screws, which are taking place on both sides of the contactor, separating the upper parts and taking the coil out off its socket. Much attention should be paid to placing on its spring that at the bottom side, during re-assembling. 

Type

Control Capacity

Rated Current @ 380V(AC3)

PCS./CTN.

CJ19-25

18KW

12A

40

CJ19-32

23KW

18A

32

CJ19-43

29KW

20A

32

CJ19-63

43KW

30A

20

CJ19-95

63KW

40A

20


 

2. Company show 

Magnetic Contactor switch cj19

 

 

 Magnetic Contactor switch cj19

 

Magnetic Contactor switch cj19

  

Workshop 

Magnetic Contactor switch cj19

  

Exhibition 

Magnetic Contactor switch cj19 

 

Certificate 

Magnetic Contactor switch cj19

 

 

 

3. Production series 

Magnetic Contactor switch cj19 

  

Magnetic Contactor switch cj19

  

4. Packing show 

Magnetic Contactor switch cj19  

....

Contact Supplier

Ms. Jane Zheng Manager Chat Now
Telephone
86-577-62865113
Mobile
13706773787
Fax
86-577-62865112
Address
Chang Jiang Road, Daqiao Industrial Zone Wenzhou,Zhejiang

You May Like

New Products

Recommended Products

View More View Less

Find Similar Products By Category

Electrical Equipment & Supplies > Contactors
Categories
Hi~