AAC Flag conductors 700MCM
USD $2,400 - $2,600 /Kilometer
Min.Order:1 Kilometer
Henan Jinshui Cable Group Co., Ltd.
AAC Flag conductors 700MCM
Code Name: Flag.
Total Area: 700MCM.
Stranding and Wire Dia.: 61/2.72mm.
Overall Dia.: 24.48mm.
Linear Mass: 978 kg/km.
Max.D.C. Resistance at 20°c: 0.0813 ohm/km.
Calculated Breaking Load: 51.46 kN.
Based standard: ASTM B231.
1. Applications
AAC conductors have been widely used in power transmission lines with various voltage levels,because they have such good characteristics as simple structure,convenient installation and maintenance,low cost large transmission capacity.And they are also suitable for laying across rivers valleys and the places where special geographical features exist.
2. Service Performance
(1).The permissible long-time operating temperature for aerial conductor is 70°c.
(2).Under the circumstance that rare climate is occuring and ice coverage rate low in heavy ice area,the biggest stress of cable at the lowest point of the sag should not exceed 60% of the short-time destructive power.
(3).When connecting conductors,the conductor beside the connecting tube cant be prominent.
Otherwise,the force on the operating conductors will be unbalanced.After connectors are install,the connecting tube should be painted by moisture-proof varnish in order to protect it from corrosion.
(4).Under installaion,the arc downing stress of all the conductors should be the same.With in the permissible distance of crossing buildings or dropping to the ground,the stress can be 10-15% higher than regular stress.
3. Product Performance
(1).The electrical performance of AAC is indicated in DCΩ/km (20oC).The resistivity of the hard aluminum wire for stranded wires is not greater than 28.264 nΩ. m of international standard value.
(2).The rated tensile strength of AAC is denoted with the result of total cross section of all aluminum conductors multiplied by min.tensile of corresponding size specified in the standard for aluminum wire.
4.Standards
(1).AAC conductors according to ASTMB231
Sizes: 6AWG,4AWG,2AWG,1AWG,1/0AWG,2/0AWG,3/0AWG,4/0AWG,
250MCM~1000MCM
(2).AAC conductors according to BS215 Part1
Sizes: 25mm2~700mm2.
(3).AAC conductors according to DIN48201
Sizes: 16mm2~1000mm2.
(4).AAC conductors according to IEC61089
Sizes: 10mm2~1000mm2