Good quality AAC, AAAC, ACSR, overhead all aluminium acsr bare conductor
Negotiable /Meter
Min.Order:1000 Meters
Henan Jinshui Cable Group Co., Ltd.
High quality bare conductor AAC, AAAC, ACSR, overhead flat conductor China power cable wire
High quality bare conductor AAC, AAAC, ACSR, overhead conductor power cable
High quality AAAC all aluminum alloy conductor electrical overhead cable
bare conductor AAC, AAAC, ACSR, overhead conductor electric cable
High quality bare conductor AAC, AAAC, ACSR, overhead flat conductor power cable
high quality AAC, AAAC, ACSR, overhead acsr bare conductor
Specifications
1 AAC: All Aluminium Conductor 2 AAAC:All Aluminium Alloy Conductor 3 ACSR:Aluminum Conductor Steel Reinforced 4 ACSR/AW
Type of conductor:
1 AAC:All Aluminium Conductors
ASC:Aluminium Stranded Conductors
2 AAAC:All Aluminium Alloy Conductors
AASC:Aliminium Alloy Stranded Conductors
3 ACSR:Aluminium Conductor Steel Reinforced
4 ACSR/AW
AAC Technical Characteristics Based on Standard DIN 48201 / DIN EN50182
Code number | Area | Number of wires | Wire diameter | Conductor diameter | Linear mass | Rated strength | D.C. resistance at 20oC |
mm2 | No. | mm | mm | kg/km | kN | Ω/km | |
16 | 15.9 | 7 | 1.7 | 5.1 | 43.4 | 3.02 | 1.7986 |
25 | 24.2 | 7 | 2.1 | 6.3 | 66.3 | 4.36 | 1.1787 |
35 | 34.4 | 7 | 2.5 | 7.5 | 93.9 | 6.01 | 0.8317 |
50 | 49.5 | 7 | 3 | 9 | 135.2 | 8.41 | 0.5776 |
50 | 48.3 | 19 | 1.8 | 9 | 132.9 | 8.94 | 0.5944 |
70 | 65.8 | 19 | 2.1 | 10.5 | 180.9 | 11.85 | 0.4367 |
95 | 93.3 | 19 | 2.5 | 12.5 | 256.3 | 16.32 | 0.3081 |
120 | 117 | 19 | 2.8 | 14 | 321.5 | 19.89 | 0.2456 |
150 | 147.1 | 37 | 2.25 | 15.8 | 405.7 | 26.48 | 0.196 |
185 | 181.6 | 37 | 2.5 | 17.5 | 500.9 | 31.78 | 0.1588 |
240 | 242.5 | 61 | 2.25 | 20.3 | 671.1 | 43.66 | 0.1193 |
300 | 299.4 | 61 | 2.5 | 22.5 | 828.5 | 52.4 | 0.0966 |
ACSR Technical Characteristics Based on Standard BS 215-2
Code name | Nominal aluminium area | Stranding and wire diameter | Sectional area of aluminium | Total sectional area | Approx. overall diameter | Approx. mass | Calculated D.C. resistance at 20oC | Calculated breaking load | |
Al | Steel | ||||||||
mm2 | No./mm | mm2 | mm2 | mm | kg/km | Ω/km | kN | ||
RABBIT | 50 | 6/3.35 | 1/3.35 | 52.88 | 61.7 | 10.05 | 214 | 0.5426 | 18.35 |
DOG | 100 | 6/4.72 | 7/1.57 | 105 | 118.5 | 14.15 | 394 | 0.2733 | 32.7 |
WOLF | 150 | 30/2.59 | 7/2.59 | 158.1 | 194.9 | 18.13 | 726 | 0.1828 | 69.2 |
DINGO | 150 | 18/3.35 | 1/3.35 | 158.7 | 167.5 | 16.75 | 506 | 0.1815 | 35.7 |
LYNX | 175 | 30/2.79 | 7/2.79 | 183.4 | 226.2 | 19.53 | 842 | 0.1576 | 79.8 |
ZEBRA | 400 | 54/3.18 | 7/3.18 | 428.9 | 484.5 | 28.62 | 1621 | 0.0674 | 131.9 |
AAAC Technical Characteristics Based on Standard BS 3242
Code name | Nominal aluminium area | Stranding and wire diameter | Sectional area | Approx. overall diameter | Approx. mass | Calculated D.C. resistance at 20oC | Calculated breaking load |
mm2 | No./mm | mm2 | mm | kg/km | Ω/km | kN | |
ALMOND | 25 | 7/2.34 | 30.1 | 7.02 | 82 | 1.094 | 8.44 |
CEDAR | 30 | 7/2.54 | 35.47 | 7.62 | 97 | 0.9281 | 9.94 |
FIR | 40 | 7/2.95 | 47.84 | 8.85 | 131 | 0.688 | 13.4 |
HAZEL | 50 | 7/3.30 | 59.87 | 9.9 | 164 | 0.5498 | 16.8 |
OAK | 100 | 7/4.65 | 118.9 | 13.95 | 325 | 0.2769 | 33.3 |
ASH | 150 | 19/3.48 | 180.7 | 17.4 | 497 | 0.183 | 50.65 |
ELM | 175 | 19/3.76 | 211 | 18.8 | 580 | 0.1568 | 59.1 |
UPAS | 300 | 37/3.53 | 362.1 | 24.71 | 997 | 0.09155 | 101.5 |