Overhead Insulated Cable 0.6/1kv copper and aluminium core conductor
Negotiable
Min.Order:1
Henan Jinshui Cable Group Co., Ltd.
Overhead Insulated Cable
Detailed Product Description
Specification:
1. Fit for the overhead circuit which rated AC voltage is 10KV.
2. The long term working temperature of the conductor; The max temperature of HPVC insulated cable is 70oC; the max temperature of HPLX insulated cable is 90oC.
3. The laying temperature should high then -20oC.
4. The permitted curving radius of cable should larger then the test cylinder of cable carving test.
5. The max temperature of cable when short circuit (less then 5 seconds) ; the max temperature of HPVC insulated cable is 150oC, and the max temperature of HPLX insulated cable is 250oC.
The detail and technical data of the products:
Type | Name |
JKYJ | Copper conductor XLPE insulated overhead cable |
JKLYJ | Aluminum conductor XLPE insulated overhead cable |
JKYJ/Q | Copper conductor XLPE thin style insulated overhead cable |
JKLYJ/Q | Aluminum conductor XLPE thin style insulated overhead cable |
Section area of the conductor mm² | Number of the thread/single thread diameter | Thickness of the insulator mm | Max diameter of the cable | The resistance of the conductor at 20 Ω/km ≤ | The resistance of the insulator at 70 | |
Cu | Al | |||||
10 | 7/1.40 | 3.4 | 0.5-- | 13.0 | -- | 3.080 |
16 | 7/1.78 | 3.4 | 0.5-- | 14.0 | -- | 1.910 |
25 | 7/2.25 | 3.4 | 0.5-1.0 | 15.2 | 0.749 | 1.200 |
35 | 7/2.60 | 3.4 | 0.5-1.0 | 16.3 | 0.540 | 0.868 |
50 | 7/3.10 | 3.4 | 0.5-1.0 | 18.0 | 0.399 | 0.641 |
70 | 19/2.27 | 3.4 | 0.5-1.0 | 19.3 | 0.276 | 0.443 |
95 | 19/2.65 | 3.4 | 0.6-1.0 | 21.0 | 0.199 | 0.320 |
120 | 36/2.16 | 3.4 | 0.6-1.0 | 22.3 | 0.158 | 0.253 |
150 | 36/2.42 | 3.4 | 0.6-1.0 | 24.0 | 0.128 | 0.206 |
185 | 36/2.68 | 3.4 | 0.6-1.0 | 26.0 | 0.1021 | 0.164 |
240 | 36/3.05 | 3.4 | 0.6-1.0 | 27.5 | 0.0777 | 0.125 |
300 | 36/3.40 | 3.4 | 0.6-1.0 | 30.0 | 0.0619 | 0.100 |