Data/Telecom DIN rail SPD
USD $1 - $10 /Piece
Min.Order:100 Pieces
Zhejiang Reyun Electric Co., Ltd.
Data/Telecom DIN rail SPD
Product introduction
LYX-R/L surge protector protect un-earthed data(asymmetrical, suspended) cable that used for dual wire electronic measurement and control and the voltage shall not exceed 110V, frequency not more than 2MHz, to prevent data cable and related equipment from being damaged duo to surging over-voltage caused by lightning or traveling wave. It is mounted between LPZ1 and LPZ3.
LYX-R/L two-stage circuit consists of gas discharging tube, piezore-sistance and claming diode, with advantage of large discharging capacity, short clamping time and low protection level.
LYX-R/L protector can be mounted on 35mm rail of different standard switching box or distribution box. It does not need screws for connecting with terminal.
Arrester | LYX-R/L | ||||
Mounting position LPZ | 1-3 | ||||
Normal voltage Un(DC/AC) | 5V | 6V | 12V | 24V | 48V |
Maxi. continuous operating voltage Uc (DC/AC) | 7V | 9V | 15V | 30V | 51V |
Voltage protective level (Up) | ≤13V | ≤20V | ≤30V | ≤51V | ≤100V |
Rated load current of category(R) | 0.2A | ||||
Rated load current of category( L) | 1.0A | ||||
Normal discharge current(8/20) In. | 10kA | ||||
Series connected resistance of each line of category (R) | 15Ω | ||||
Series connected resistance of each line of category (L) | 100μH | ||||
Cross sectional area of connected conductor | 0.14-2.5mm2 | ||||
Peel-off length for the wire to be connected | 6-7mm | ||||
Color | Grey | ||||
Material | Fire resistant reinforced PC | ||||
Applicable standard | IEC61643-21 |