800/5A Class 1.0 Current Transformer for Measuring
USD $3.8 - $5.85 /Piece
Min.Order:1 Piece
Yueqing Yomin Electric Co., Ltd.
800/5A Class 1.0 Current Transformer for Measuring
Model: MSQ-60-800/5-CL1.0
Current Transformer (CT) is used to transform the high AC current to small easily manageable values. They're connected with the Panel Meter or Relay and they can help to measure the current or protect the equipments. Low voltage current transformers are manufactured as of two types for measuring CT.
Selection of the Current Transformer
To select the current transformer correctly, the following points should be clarified:
Power Losses of the CT
In the practical application, the power generated by the primary current should be equal or bigger than the power requirement of the associated measuring device plus the consumption of the connecting line.
Losses in the line, PL:
This is the power loss, through heat, generated by current through the resistance RL in the cable, in the transformer’s secondary circuit.
Factors to be taken into account:
Secondary current: PL = RL / 2
Cable diameter: RL is inversely proportional to the square of the diameter cable length: RL is proportional to the length of cabling (there and back).
Power: The nominal apparent power (VA) with a specified power factor, which was supplied by the Current Transformer, to the secondary current with the assigned current when it is connected to its nominal load. Sc (VA) = Zc (/sn)2 According to Standards, for apparent power greater than or equal to 5VA, the power factor is 0.8 inductive. For apparent power less than 5VA the power factor is considered to be one (unity).
Accuracy of A Current Transformer
The percentage of error, produced in a transformer, is established by IEC60044-1. In measurement transformer: 25% and 100% of nominal power. In protection transformers: 100% of nominal power.
Note: with…/1A transformers losses are reduced 25 times.
Saturated Condition of CT
The current transformer is saturated if the primary current, passing through the CT, is greater than the nominal rating of the CT.
The linearity of CT, between the primary and secondary sides decreases, so error increases. The saturation of the CT is inversely proportional to the load (FIG. 1).
The difference between measuring and protection current transformers is their behavior when an overload occurs on the primary side. Measuring CT is saturated when there is a primary current overload. In order to protect the equipment. On the secondary side, protection CT will not saturated until there is a very high current on the primary side, A class 5P15 protection transformer indicates that it has an accuracy rating of ±1% that it does not become saturated until the primary current reaches 15 times the nominal current rating of the CT.
In measuring transformers, the SAFETY FACTOR “FS” parameter indicates the excessive amperage on the primary side current in relation to the current sent to the measuring device on the secondary side.
Application Note
If the primary current is too small, to keep the same accuracy and output, we can add primary winding, but the rated turns ration should be the same, For example, if the primary current is 50A, we can use 100/5A current transformer with the primary current be turned twice which help to keep the same rated turns ratio (1:50 = 2:100).
Construction
CT consist of primary winding, secondary winding, magnetic core and insulated body. The high-grade silicon steel core is annealed, varnished then insulated with polycarbonate core caps. The secondary winding is toroidally wound by high precision semi-automatic machinery. For the tape wound ring type current transformer, the PEW coated windings are then covered with elephantite paper, varnished and double-tapped with PVS tapes. For the encapsulated type current transformer, the windings are enclosed in a compact and heat resistant split cap.
Item | Current Ratio | Rated Burden (VA) | Case Qty. | |
Model | (A) | Class: 0.5 | Class: 1.0 | (Pcs) |
MSQ-60 | 250/5 | 1.5 | 2.5 | 32 |
MSQ-60 | 300/5 | 2.5 | 5 | 32 |
MSQ-60 | 400/5 | 5 | 10 | 32 |
MSQ-60 | 500/5 | 5 | 10 | 32 |
MSQ-60 | 600/5 | 5 | 10 | 32 |
MSQ-60 | 750/5 | 5 | 10 | 32 |
MSQ-60 | 800/5 | 7.5 | 10 | 32 |
MSQ-60 | 1000/5 | 10 | 15 | 32 |
MSQ-60 | 1200/5 | 10 | 15 | 32 |
MSQ-60 | 1500/5 | 15 | 15 | 32 |
MSQ-60 | 1600/5 | 15 | 15 | 32 |
Note:
Class and VA rating must be mentioned when ordering.
Thank you for viewing this listing.
Please take a moment to review our other items.
Add us to your favourite sellers list, many thanks!
If you would like to find out more details of our products, please feel free to contact me by mobile: 0086 13968745210