NATURAL GAS GENSET ON STOCK
USD $230,000 - $250,000 /Set
Min.Order:1 Set
Fujian Fuan Mindong Yanan Electric Machine Co., Ltd.
Technical data sheet
Model : NG1000 ISO3046 ISO8528 IEC34 BS EN 60034 BS5000 | prime power | kW/kVA | 1000/1250 | |
standby power | kW/kVA | 1100/1375 | ||
frequency/speed | Hz/rpm | 50/1500 | ||
rated voltage | V | 400/230 | ||
rated/maximal current | A | 1804/1985 | ||
connection |
| 3P4W | ||
power factor |
| 0.8 |
| |||
Engine | MTU16V165RQS | Standard filter, start DC motors, charging motor | |
Alternator | Yanan SLG454A | MX321(AVR) | |
Cooling system | Heat exchanger | 40 ℃ standard ambient temperature | |
Control system | WOODWARD | control panel | |
Tank base | YANAN | Elastic shock absorbers, starting battery holder | |
Starting battery | Lead-acid | Battery connection cable,the capacity more than 6 times | |
Muffler | Industrial | Standard stainless steel corrugated hose, flanged hot pad | |
Files |
| drawings, unit operation and maintenance manual, certificate, etc. | |
Auxiliary equipment | Flame arresters, voltage regulator valves, manifold solenoid valves, flow valves, pressure gauges, etc. | ||
Auxiliary equipment for exhaust system | Exhaust bellows, explosion-proof doors |
Data | Prime power/standby power | KW | 1100/ 1210 | ||||
| Model |
| 4-stroke 90 ° V-type 16-cylinder gas engine | ||||
| aspiration |
| Turbocharged and intercooled air | ||||
| Bore*stroke | mm | 165×185 | ||||
| Displacement | L | 63.36 | ||||
| Compression ratio |
| 11:1 | ||||
| Rated speed | RPM | 1500 | ||||
| Speed governor |
| Electric(≤±0.25%) | ||||
| Starting |
| DC24V 15KW | ||||
| Power Efficiency |
| 34.8% | ||||
| Mechanical efficiency |
| 40% | ||||
| Maximum allowable exhaust backpressure | mbar | 50 | ||||
| Exhaust gas temperature(prime / standby) | ℃ | 620 | ||||
| Gas consumption |
|
Type |
| Double- bearing |
Excitator |
| Brushless Self-exciter |
Steady-state voltage regulation rate | % | ≤±1 |
Insulation Class |
| H |
Protection class |
| IP21 |
Power factor |
| 0.8 |
Power efficiency | % | 95.2 |
Poles |
| 4 |
Waveform distortion | % | No load<1.5,non-distorting balanced linear load<5 |
THF/TIF |
| THF<2% TIF<50 |
control cabinet
Operation system(LOP)
features and performance
Ambient condition
Atmospheric pressure 0.1MPa Ambient temperature - 30~ +55 ℃
Relative humidity <95% Protection class IP44
Performance
Operating meter box is short for Monitoring meter box;The box is included of gas engine operation, performance monitoring, security, and uploads communications and pre-supply of oil, the starter output relay systems,etc
l The box is manufactured in accordance with the relevant electrical standards and can be adapted to the requirements of gas engines.
Under normal environmental conditions, all of the various components should be reliable, display The monitor is with a resolution of 240 × 128 pixels,
monochrome LCD.
l Sensors and measuring channel level of accuracy and range
Temperature 1.5 0 ~ 120 ℃
Oil pressure 1.5 0 ~ 1 Mpa
Cooling water pressure 1.5 0 ~ 0.7 Mpa
Intake pressure 1.5 0 ~ 0.4 Mpa
Speed ±1 r/min 0 ~ 3000 r/min
A/B Exhaust temperature 1.5 0 ~ 800 ℃
16Single-cylinder exhaust temperature 1.5 0 ~ 800 ℃
Under -30~+55℃ ambient conditions can reliable running,good antijamming capability,and have running data monitoring function such as gas engine
over speed.high water Temperature ,high oil Temperature ,low oil pressure.A/B high exhaust Temperature ,each cylinder Temperature display,
cool water level ,It will be make a sound,light alarm and provide stop signal to Woodward EGS-02 control systems when the running data exceed the rated value,then protect the engine or emergency stop
l Protection
Overspeed ≥ 1650r/min Alarm ≥1725r/min Alarm and transfer emergency stop signal
Lub Oil pressure ≤ 0.42 MPa Alarm ≤0.37MPa Alarm and transfer emergency stop signal
Cooling Water pressure ≤ 0.12 MPa Alarm
Cooling Water Temperature ≥ 85℃ Alarm ≥90℃ Alarm and transfer emergency stop signal
Lub Oil Temperature ≥ 105℃ Alarm and transfer emergency stop signal
Intake air temperature ≥ 77℃ Alarm and transfer emergency stop signal
exhaust gas temperature ≥ 640℃ Alarm and transfer emergency stop signal
Cooling Water Level Alarm and transfer emergency stop signal
l The engine start speed ≤600r/min,the system will not be false alarm
l Engine running time
l Monitoring meter use WOODWARD company EGS-02,IC92 and Shanghai yunfei products,panel has power switch,start,pre-provide button, emergency stop butto,reset,self-checking,noise reduction/timekeeping button, trimmer potentiomete,jigger and grain(will be use on maitenance)and kinds of alarm indication .Monitoring meter Power:DC24V(±20%).
Gas fire control system
WOODWARD EGS-02 is the most advanced technology of gas fire control,can suitable for two type flammable gas to switch,the system including Intelligent high-energy ignition system,Ignition coil of Merck teck Germany,original Japanese high energy ignition plugs,Tecjet gas flow jet regulationg valve, WOODWARD electric speed govenor control system and use ProAct-ITB digital integrated throttle executive component, venturi-mixed reactor,upper machine ect.make up automatic and security protection closed-loop control system.Achievable lean burn, avoid intake-tube temper,improve efficiency,reduce thermal load.engine monitoring system with standard communication interface RS485 and communication protocol.