2013 E+H 4-20mA pressure transmitter FMB51
Negotiable /Piece
Min.Order:1 Piece
Xian Wellwork Industrial Co., Ltd.
E+H 4-20mA pressure transmitter FMB51
Hydrostatic level measurement
Pressure sensor with the CONTITETM measuring cell
Condensate-resistant offering long-term stability; communication
via HART, PROFIBUS PA or FOUNDATION Fieldbus.
Your benefits
Very good reproducibility and long-term stability
Turn down 100:1
Hermetically sealed CONTITETM measuring cell:
- Condensate-resistant and climatic-proofed
- High reference accuracy: ±0.2 %, optionally ±0.1 %
- Minimum temperature effects
End-to-end modularity for differential pressure, hydrostatics and pressure (Deltabar M - Deltapilot M - Cerabar M), e.g.
- replaceable display
- universal electronics
Easy commissioning without the need for an operating tool
Usage in drinking water: KTW, NSF
Used for process pressure monitoring up to SIL2,
certified to IEC 61508 Edition 2.0 and IEC 61511 by
TÜV NORD
The hydrostatic pressure sensor is used for the following measuring tasks:
Level, volume or mass measurements in liquids
Measuring Principle | Hydrostatic | |
Characteristic | Pressure transmitter for pressure or hydrostatic level measurement with flush mounted metallic CONTITE measuring cell: - hermetically welded - absolute condensation tight - climate-resitant - long-term stable - Lowest temperature influences Rod version | |
Supply / Communication | 4...20mA HART: 10,5...45V DC Ex ia: 10,5...30V DC PROFIBUS PA / FOUNDATION Fieldbus: 9...32V DC (Non Ex) | |
Accuracy | Standard 0,2% Optional 0,1% | |
Long term stability | 0,05% of URL/year | |
Process temperature | -10°C...85°C (14°F…212°F) | |
Ambient temperature | -40°C...85°C (-40°F...185°F) | |
Measuring range | 100mbar...10bar (1.5psi...150psi) | |
Max. overpressure limit | 40 bar (600 psi) | |
Process connection | Thread: G1 1/2, MNPT1 1/2 Flange: DN40...DN100, ASME 2"...4", JIS 10K | |
Output | 4...20 mA HART PROFIBUS PA FOUNDATION Fieldbus | |
Certificates / Approvals | ATEX, FM, CSA, CSA C/US, IEC Ex, TIIS, INMETRO, NEPSI Overfill prevention WHG SIL EN10204-3.1 NACE Drinking water | |
Options | Separate housing Initial device settings Overvoltage protection | |
Specialities | Modularity to differential pressure and process pressure devices (replacable display, universal electronics) diagnostic functions Hermetically sealed Contite measuring cell (condensate-resistant and climatic-proofed) | |
Application limits | If pressurized, usage of two pressure transmitters to measure the differential pressure (electronic dP) Observe ratio head pressure : hydrostatic pressure |