fixed expansion valve(BV)
USD $15 - $35 /Piece
Min.Order:1 Piece
Shanghai Thermostat Factory Co., Ltd.
fixed expansion valve
The BV Discharge-bypass valve is used in the refrigerating system, which is not equipped with unloading device for the system load adjustment.
l The BV Discharge-bypass valve can be used as automatic expansion valve under fixed pressure to maintain the fixed evaporation pressure (temperature).
l The BV Discharge-bypass valve is capable to maintain the minimum evaporating pressure.
l SAE and ODF connecting .
l Suitable for HFC and HCFC
l Maximum working pressure: 30bar.
Technical data
| Adjustable range | Nominal Liquid Capacity (kW) | Setting pressure | Connecting size | |
R134a | R22 | ||||
| 0~7 Bar | 1.5 | 2.8 | 4Bar | ODF Inlet:φ8×1 Outlet:φ10×1 |
| 2.4 | 4.5 | |||
| 3 | 5.6 | |||
| 4.2 | 8.4 | |||
| 5.7 | 11.2 | |||
| 8.5 | 16.8 |
Function
The BV-type Discharge- bypass valve can open or close automatically while outlet pressure varies to ensure the outlet pressure constant on the setting point regardless of the change of the inlet pressure (within a certain range).
BV used as expansion valve under the fixed pressure
|
BV used as throttling valve to regulate energy
The inlet of the BV Discharge-bypass valve is connected to the discharge pressure, and the outlet to the outlet or inlet of evaporator (Equivalent to extract pressure). Under this condition, the BV is closed when evaporator loading; Because of decreasing evaporate pressure with a period of operation of the compressor, that is, it requires less power of the compressor because the expansion valve throttle turns to smaller, the evaporating pressure also becomes lower. When lowering than the set value,BV is opened automatically. Parts of discharge gas of the compressor are by-passed to the inlet or outlet of evaporator.
BV functioned as regulate energy
In the process of loading and unloading described as above, in case that the compressor operates in the period when evaporator lowers the load, the evaporating pressure (less than 4bar) is increased to 4bar. The pressure drop decreasing between the discharge and suction reduce load of the compressor resulting in energy saving.
Suggestion of assembly
l Bypass the hot gas to the inlet of the evaporator to increase temperature of the outlet of the evaporator, enhance supplying liquid volume and decrease temperature of the extract air.
l Or add the injection valve to regulate the injection liquid to distribute parts of refrigerant entering into the suction tube to absorb heat from evaporator, thus reducing the temperature of the discharge gas