Specifications
Specifications
1.High voltage: 6KV/10KV/35KV, low voltage: 380V220V
2.Safe, reliable, no pollution
Performance Feature
1, High voltage:6KV/10KV,/35KV low voltage:380v 220v
2. Safe, reliable, no pollution, can operate directly in the load center
3. High mechanical strength, strong ability to withstand short circuit, low partial discharge, good thermal stability, high reliability, long use life;
4.Low no-load loss, high performance, low noise, efficient energy conservation;
5. High thermal performance, high operation capacity, forced air cooling can improve the operation of capacity.
6. Good moisture resistant ability, can operate in high humidity and other harsh environments
7. With features of environmental protection, flame retardant, explosion- proof and free of maintenance;
8. Small size, light weight;
- This kind of substation is a compact and complete set of distribution device which consists of 12kv High-voltage power distribution equipment, a 12/0.4kv power transformer, low-voltage power distribution equipment, and electric energy metering equipment.
- It mainly apply to 50Hz,6-12/0.4kv three phase current power system as power or lighting supply. It especially applies to transforming the distribution circuit on both sides of the road. Residential districts, streets, large scale sites, high-rise buildings, industrial and mining enterprises, temporary facilities , etc, are all appliable.
- This product conforms to GB/T17467, IEC601330.
- Functional characteristics: Compact structure, covers an small area, high strength, convenient in transportation and installation. Users can choose different structure according to their demands.
- The cabinet of the substation can be made in two kinds of materials: steel plate or aluminum alloy. The carriage is welded by molding steel or connected by bolts. And it can be divided into high-pressure chamber, transformation chamber, low-pressure chamber. The bottom is welded by steel channel and the overall structure strength high. The door and outers is made of steel plate, aluminum alloy or composite board. They are embalmed and meet the requirement of outdoor long-term use. They also can make sure the performance of water-proof, dustproof and corrosion prevention. There are ordinary type and landscape type of shape designs for applying in different occasions. The shell of the substation is equipped with ventilation, heat-off, particle filtering devices. Room temperature monitoring and condensation prevention devices can be installed if asked.
Data
Item | Parameters |
Frequency/HZ | 50 |
Rated Voltage/kV | 6 | 10 | 35 |
Max Voltage/kV | 6.9 | 11.5 | 40.5 |
Power Frequency Withstand Voltage/kV | 32/36 | 42/48 | 95/118 |
| | | |
Lightning Impulse Withstand Voltage/kV | 60/70 | 75/85 | 185/215 |
| | | |
Rated Current/A | 400/630 |
Rated Short-time Current/KA | 12.5(2S) 16(4S) 20(2S) |
Rated Peak Withstand Current/KA | 32.5-40- 40.5 |
Rated Voltage/V | 380/220 |
Rated Current Of Major Loop/A | 100-3200 |
Rated Short-time Current/KA | 15-30-50 |
Rated Peak Withstand Current/KA | 30-63-110 |
Branch Current/A | 100-800 |
Duplexure/Loop | 1-12 |
Compensation Capacity/KVar | 0-360 |
Rated Capacity/KVA | 50-2000 |
Short Circuit Resistance/% | 4/6 |
Tap Ranges of High Voltage/% | ±5;±2*2.5 |
Connection Symbol | Yyn0;Dyn11 |