280kw silent diesel generator price list for sale Quality Choice
USD $33,000 - $38,000 /Set
Min.Order:1 Set
Taizhou Sutech Power Machinery Co., Ltd.
280kw silent diesel generator price list for sale
(High quality, Original engine, Low fuel consumption)
Powered by Perkins engine
Every generator set is subjected to a comprehensivetest program which includes 50% load, 75% load,100% load, 110% load and the checking and proving of all control and safety shut-down functions;
24V DC start motor;
Equipped with battery charger and 24V highperformance maintenance-free lead-acid startingbatteries and connecting with cables;
Equipped with industrial silencer and flexible exhaust hose;
Equipped with CHINT MCCB circuit breaker;
Designed to Comply with ISO8528/GB2820;
Powered by UKP engine,Controlled by Deepsea panel
Voltage | HZ | Phase | P.F (COS) | Output (KVA) |
380/220V | 50 | 3 | 0.8 | 350 |
Remark | 60Hz, 220, 380V, 460V, 480V, 600V can be produced as requirements. |
280kw silent 2206C-E13TAG2 generator with original Perkins engine
Engine Model | 2206C-E13TAG2 |
Number of Cylinders | 6 cylinders, vertical in line |
Cycle | 4 stroke |
Aspiration | Turbocharged and after water cooled |
Bore×Stroke | 130mm x157mm |
Displacement | 12.5L |
Compression ratio | 16/3:1 |
Prime Power/Speed | 305KW / 1500rpm |
Standby Power/Speed | 349KW / 1500rpm |
Speed Governor | Electrical |
Cooling System | Forced water cooling cycle |
Steady speed droop | ≤1% |
Total lubrication system capacity | 40L |
Coolant capacity | 51.4L |
Fuel Consumption at 100% Load | 209g/kw.h |
Starter Motor | DC24V, |
Alternator | DC24V |
Alternator brand | Stamford, Marathon, Leroy Somer, Mecc-alte, TWGII… |
Prime power | 375KVA |
Frequency/speed | 50HZ/1500rpm (60Hz/1800rpm) |
Exciter type | Single bearing, Brushless, Self-excited |
Power factor | 0.8 |
Voltage adjust range | ≥5% |
Voltage regulation NL-FL | ≤±1% |
Insulation Grade | H |
Protection Grade | IP23 |
Phase / wire | 3 phase 4 wires |
The control module gives digital readouts of:
Generator voltage;
Output frequency;
Engine speed;
Battery voltage;
Engine hours run.
The control module has indicators for failure
information:
Overspeed/underspeed,
Emergency stop
Low oil pressure;
High water temperature
Failure to start
Battery charger failure
Automatic shutdown occurs under:
Low engine oil pressure;
High engine water temperature;
Overspeed/underspeed;
Failure to start after three attempts.
Soundproof for optional