1.General description
Our K series switchgear can be divided into two types: fixed type and unit-combination extendable type. With perfect corrosion resistant enclosure and sealing, it can be used in various places.
2. standards:
International standard:
IEC60376 IEC60129 IEC60298 IEC60265-1 IEC60420 IEC60694 IEC60282 IEC60056 DINVDE0670 (German standard)
National standard:
GB11022 GB3906 GB1984 GB3804 GB16926
3.specification:
Item | K Module Cable | T Module Transformer | V Module Circuit Breaker | ||
Rated voltage (KV) | 12/24 | 12/24 | 12/24 | ||
Rated frequency (Hz) | 50/60 | 50/60 | 50/60 | ||
1min power frequency withstand voltage (KV) | 50/60 | 50/60 | 50/60 | ||
Lightning impulse withstand voltage (KV) | 125/145 | 125/145 | 125/145 | ||
Rated current (A) | 630 | ≤200 | 630 | ||
Rated active load breaking current (A) | 630 |
| 630 | ||
Rated closed-loop breaking current (A) | 630 |
| 630 | ||
5%active load breaking current (A) | 31.5 |
| 31.5 | ||
Rated cable charging breaking current (A) | 50 |
| 50 | ||
Rated transfer breaking current (A) |
| 1700/2700 |
| ||
Rated short circuit breaking current (KA) |
|
| 20 | ||
Rated short circuit making current (KA) | 50 |
| 50 | ||
Rated short-time withstand current (KA) | 20/25 |
| 20/25 | ||
Rated short-time duration (S) | 4/3 |
| 4/3 | ||
Rated withstand current (peak value) (KA) | 50 |
| 50 | ||
Mechanical life (time) | 5000 |
| 10000 | ||
Environment temperature (centigrade) | -40~+55 centigrade | ||||
SF6gas pressure/ 20 centigrade gage pressure (MPa) | 0.03 | 0.03 | 0.03 | ||
IP | Gas tank IP67,others IP3X | ||||
Annual leakage rate | ≤0.004% |