Description of Pole Type Terminal box:
Main Technical Data:
Ex mark | Ex e II C T6 Gb Ex tD A21 T80℃(Ex e) Ex ia/ib II A, II B, II C, Ga/Gb Ex tD A20(Ex i) |
Intended use | Can be used in zone 0, zone 1, zone 2, zone 20 zone 21 and zone 22 |
Degree of protection | IP66 |
Rated voltage | AC 690V |
Rated current | max 35A |
Ambient temperature use | -40 ℃ ≤ Ta ≤ 55 ℃ |
Type of terminal | Pole type |
Cross section of terminal | 4mm2/25A(The most conductors which can be connected to the pole type terminal are four wires) 6mm2/32A(The most conductors which can be connected to the pole type terminal are two wires) |
Earthing terminal | 2x4mm2 |
Material | Alloy plastic of static resistence |
Order Specification:
Description of Cage Type Terminal box:
Main Technical Data:
Ex mark | Ex e II C T6/T5 Gb Ex tD A21 T80℃/T95℃ (Ex e) Ex ia/ib II A, II B, II C, Ga/Gb Ex tD A20(Ex i) |
Intended use | Can be used in zone 0, zone 1, zone 2, zone 20, zone 21 and zone 22 |
Degree of protection | IP66 |
Rated voltage | AC 690V |
Rated current | max 35A |
Ambient temperature use | -40 ℃ ≤ Ta ≤ 40℃(55℃) |
Cross section of terminal | 1.5mm2/16A; 2.5mm2/20A; 4mm2/25A; 6mm2/32A |
Max terminals: | 1.5mm2/15pcs; 2.5mm2/15pcs; 6mm2/10pcs |
Earthing terminal | 2x4mm2 |
Material | Alloy plastic of static resistence |
Order Specification:
Company information: