Multimedia Lightning Protection Socket
USD $20 - $30 /Set
Min.Order:1 Set
Hunan Zhongpu Lightning Protection Co., Ltd.
1. APPLICATION
It is mainly used for all kinds of electronic equipments for both office and home such as computers, telecom communications equipments, modems, fax machines, luxurious stereos, televisions, image equipments, scanners, printers, duplicating machines.
2.TECHNICALS PARAMETERS
Model DXH06- | Z10/5K | Z20/7K |
Max. Continuous Operating Voltage(Uc) | 320VAC | |
Nominal Continuous Operating Voltage(Un) | 250VAC | |
Nominal Power | 2500W | |
Nominal Current | 10A | |
Nominal Discharge Current Capacity (In) | 5kA(8/20μs) | 10kA(8/20μs) |
Max. Discharge Current Capacity (Imax) | 10kA(8/20μs) | 20 kA(8/20μs) |
Protection Mode | L~N L~PE N~PE | |
Response Time(T) | <25ns | |
Protection Level(Up) | ≤100V | |
Fault Indicator | Available | |
Grounding Resistance(R) | ≤4Ω | |
No. of the socket contact | 8 | 7 |
Switch | Available | |
Wire Length(m) | 2 | |
Protection Level of the Shell | IP20 | |
Operating Temperature | -40℃~+70℃ | |
Overall Size(mm) | 233×90×35 | 485×64×55 |
3.Installation Method and Attentions
1) Wiring as shown in Figure;
2) The connecting lead shall use many strands of copper wires of more than 6mm2, and the earth wire shall use many strands of copper wires of more than 10mm2. The connecting wire shall be as short, straight and coarse as possible. Grounding Resistance should be no less than 4Ω;
3) The front of lightning arrester shall be connected with proper fuse in series or be opened;
4) The power supply must be cut off while conducting the installation. It is prohibited to conduct the operation with the charge. The connecting lead must conform to the requirement;
5) After completing the installation, the lightning protection module shall be inserted tightly and inspected;
6) When there is RED for the fault indicator of the lightning arrester module (warning signal of remote-signaling port), it indicates that the lightning protection module has degraded and shall be replaced;
7) The SPD needn't special maintenance, but only check the connection and indicating state periodically.
4. Attentions:
Please make sure the power of the lightning protection socket is off when you are checking or processing damage.
5. Certificates: