6kV~35kV cold shrink series joint

6kV~35kV cold shrink series joint

USD $15 - $1,000 /Piece

Min.Order:1 Piece

Supply Ability:
10000 Piece / Pieces per Month
Port:
Shanghai or Shenzhen
Payment Terms:
T/T

Quick Details View All >

Place of Origin:
Hunan, China
Brand Name:
Changlan
Model Number:
JLS
Conductor Material:
Other, copper or Al
Insulation Material:
XLPE
Jacket:
PVC

Changlan Electric Technology Co., Ltd.

Business Type: Manufacturer,Trading Company
Changsha Hunan China
Main Products: power cable termination and joint ,cold/heat shrink cable termination and joint ,cable laying machine ,cable metal fitting ,insulation/semi-cond. /waterproof Tape

Product Details

Specifications

6/6kV, 6/10kV, 8.7/10kV, 8.7/15kV, 12/20kV, 18/20kV,18/30kV,21/35kV, 26/35kV cold shrink Termination Kit.

materials of performance

No.

Item

Value

Testing standard

Insulation material

Semi-cond. material

1

Tensile strength MPa

6.5

6

GB528

2

Elongation at break %

600

600

GB528

3

Shore hardness A

50

55

GB531

4

Tearing strength N/mm

30

30

GB/T530

5

Volume resistivity  Ω·cm

1014

103

GB692

6

Dielectric constant(50Hz)

2.8-3.5

 

GB693

7

Dielectric loss angle tangent

0.005

 

GB693

8

The leakage resistance mark

1A3.5

 

GB6553

 

products electric performace:

Test items

Standard requirement

8.7/10 8.7/15kV

12/20kV

18/20(30)kV

26/35kV

Power frequency voltage test 5min

39kV, no flashover and no breakdown

54kV, no flashover and no breakdown

81kV, no flashover and no breakdown

117kV, no flashover and no breakdown

Partial discharge test(room temperature)

15kV, 10pC

20kV, 10pC

30kV, 10pC

45kV, 10pC

Impulse voltage test (95-100°C)

95kV

125kV

170kV

200kV

Heating cable conductor to 95-100°C,each 10 times for positive and negative pole, no flashover and no breakdown

Constant pressure loading cycling voltage test (in air)

23kV

30kV

45kV

65kV

Heating cable conductor to 95-100°C, 8h for each cycling include 5h for heating and 3h for cooling. Totally 3 circulation

High temperature partial discharge voltage under room temperature

15kV

20kV

30kV

45kV

Heating cable conductor to 95-100°C, 10pC

Constant pressure loading cycling voltage test (in air)

23kV

30kV

45kV

65kV

Heating cable conductor to 95-100°C, 8h for each cycling include 5h for heating and 3h for cooling. Totally 60 circulation

Note: for the cable joint, 30 circulation in water and 30 in air

High temperature partial discharge voltage under room temperature

15kV

20kV

30kV

45kV

Heating cable conductor to 95-100°C, 10pC

Lighting impulse voltage test

95kV

125kV

170kV

200kV

each 10 times for positive and negative pole, no flashover and no breakdown

15min AC voltage withstand test

23kV, no flashover and no breakdown

30kV, no flashover and no breakdown

45kV, no flashover and no breakdown

65kV, no flashover and no breakdown

1min outdoor termination in rain power frequency voltage test

35kV, no flashover and no breakdown

48kV, no flashover and no breakdown

72kV, no flashover and no breakdown

104kV, no flashover and no breakdown

Salt spray test for outdoor termination

11kV, no flashover and no breakdown

15kV, no flashover and no breakdown

22.5kV, no flashover and no breakdown

32.5kV, no flashover and no breakdown

Salt spray test for indoor termination

11kV, no flashover and no breakdown

15kV, no flashover and no breakdown

22.5kV, no flashover and no breakdown

32.5kV, no flashover and no breakdown

 

 

suitable range:

Our cold shrinkable series products are suitable for:

Rated voltage: 6/6kV,6/10kV, nominal cross section: 35-1600mm2

Rated voltage: 8.7/10kV,8.7/15kV, nominal cross section: 25-1600mm2

rated voltage: 12/20kV,18/20(30)kV, nominal cross section: 25-1600mm2

Rated voltage: 21/35kV,26/35kV, nominal cross section: 25-1400mm2

both for single core and three cores XLPE insulation and rubber insulation power cable

environment and conditions:

Environment pollution grade: IV pollution area

Insulation level,carrying capacity,long-term working temperature and short circuit temperature can meet the technical requirement of matching cable

standard:

IEC60502, GB/T12706

feature:

According to client’s requirement, we can provide:

  1. insulation cold shrinkable cable joint, used for reduce the induced voltage and ring current on cable metal sheath of single core cable
  2. enhanced waterproof cold shrinkable cable joint, used for humid and rainy areas where need to strengthen the waterproof specially
  3. for the outer sheath, it includes waterproof tape and armoured tape type,heat shrinkable type and casting shell type, recommend the waterproof tape and armoured tape type
  4. copper braid tape will be fixed by copper binder or constant force spring hoop

 

Contact Supplier

Mr. Richard Xiao Manager Chat Now
Telephone
0086-731-85541801
Mobile
0086-13755180797
Fax
0086-731-85554380
Address
Lu Valley high-tech industrial Park, TongZiPo West Road, No. 223 Changsha,Hunan