MUSH-4 module

MUSH-4 module

Negotiable

Min.Order:1

Supply Ability:
0 per Month

Quick Details View All >

Place of Origin:
Ukraine
Brand Name:
ARTON
Model Number:
MUSH-4
Usage:
Fire

ARTON PRIVATE ENTERPRISE

Business Type: Manufacturer
Main Products: fire detectors ,FACP ,smoke detectors ,heat detectors ,manual call points

Product Details

Specifications

Auxiliary module for 2-sensor smoke detectors

MUSH-4

MODULE

The module is designed to receive alarm messages from SP-2.4 detectors, separately from upper (AL1) and lower (AL2) sensors, continuity control of AL1 and AL2 and transmission ALARM and FAULT signals to FACP with galvanic outputs.

 

The module provides:

-          voltage stabilization  for 15/24 V AL (set by a user with the “15/24 V” switch on the module PCB);

-          current restriction when short-circuit occurs in AL;

-          automatic deenergizing of AL1 and AL2 on  detecting short-circuit in any of them;

-          storage of current in AL1 and AL2 corresponding to the normal state;

-          indication of statuses “NORM”, “FIRE”, “SHORT-CIRCUIT”, “OPEN-CIRCUIT” separately for AL1 and AL2;

-          manual resetting simultaneously of AL1 and AL2;

-          decrease of the resistance value between screw contacts “Tr1+”- “Tr1-” and (or) “Tr2+”- “Tr2-” when  the alarm condition occurs correspondingly in AL1 and (or) AL2;

-          increase of the resistance value between screw contacts “Av1+” – “Av1-“ and (or) “Av2+” – “Av2-“ when any fault occurs correspondingly in AL1 and (or) AL2 and the module is deenergized.

 

TECHNICAL SPECIFICATIONS

Rated voltage

12 V

Voltage range for the module’s  proper operation

10,2-13,8 V

Voltage range powering 2-wire loop in standby mode

-          “15/24 V” jumper switch is fitted

-          “15/24 V” switch is removed

 

24±0,24 V

15±0,15 V

2-wire circuit current, the module detects SHORT-CIRCUIT in AL

>27 mA

2-wire circuit current, the module detects OPEN-CIRCUIT in AL

<5,0 mA

Absolute value of intermittent current change, the module detects FIRE status

≥ 2,8

2-wire loop resistance (not considering remote unit resistance), the module keeps proper operating

≤470 Ohm

Reset time for detectors

5±1 sec

Start-up time for detectors after resetting

5±1 sec

Max number of smoke/heat detectors per loop

32

Standby current consumption

≤100 mA

Alarm current consumption

≤200 mA

Voltage commutated by outputs

≤30 V

Current commutated by outputs

≤30 mA

Voltage drop on open outputs contacts at 20 mA

2 V

Resistance between closed outputs contacts, kOhm

≥50 kOhm

Dimensions

120x80x30 mm

Weight

200 g

Ambient temperature range

From 1 to 40 °c

Relative air humidity at 35 °c

≤95 %

 