MUSH-4 module
Negotiable
Min.Order:1
MUSH-4
MODULE
The module is designed to receive alarm messages from SP-2.4 detectors, separately from upper (AL1) and lower (AL2) sensors, continuity control of AL1 and AL2 and transmission ALARM and FAULT signals to FACP with galvanic outputs.
The module provides:
- voltage stabilization for 15/24 V AL (set by a user with the “15/24 V” switch on the module PCB);
- current restriction when short-circuit occurs in AL;
- automatic deenergizing of AL1 and AL2 on detecting short-circuit in any of them;
- storage of current in AL1 and AL2 corresponding to the normal state;
- indication of statuses “NORM”, “FIRE”, “SHORT-CIRCUIT”, “OPEN-CIRCUIT” separately for AL1 and AL2;
- manual resetting simultaneously of AL1 and AL2;
- decrease of the resistance value between screw contacts “Tr1+”- “Tr1-” and (or) “Tr2+”- “Tr2-” when the alarm condition occurs correspondingly in AL1 and (or) AL2;
- increase of the resistance value between screw contacts “Av1+” – “Av1-“ and (or) “Av2+” – “Av2-“ when any fault occurs correspondingly in AL1 and (or) AL2 and the module is deenergized.
TECHNICAL SPECIFICATIONS
Rated voltage | 12 V |
Voltage range for the module’s proper operation | 10,2-13,8 V |
Voltage range powering 2-wire loop in standby mode - “15/24 V” jumper switch is fitted - “15/24 V” switch is removed |
24±0,24 V 15±0,15 V |
2-wire circuit current, the module detects SHORT-CIRCUIT in AL | >27 mA |
2-wire circuit current, the module detects OPEN-CIRCUIT in AL | <5,0 mA |
Absolute value of intermittent current change, the module detects FIRE status | ≥ 2,8 |
2-wire loop resistance (not considering remote unit resistance), the module keeps proper operating | ≤470 Ohm |
Reset time for detectors | 5±1 sec |
Start-up time for detectors after resetting | 5±1 sec |
Max number of smoke/heat detectors per loop | 32 |
Standby current consumption | ≤100 mA |
Alarm current consumption | ≤200 mA |
Voltage commutated by outputs | ≤30 V |
Current commutated by outputs | ≤30 mA |
Voltage drop on open outputs contacts at 20 mA | 2 V |
Resistance between closed outputs contacts, kOhm | ≥50 kOhm |
Dimensions | 120x80x30 mm |
Weight | 200 g |
Ambient temperature range | From 1 to 40 °c |
Relative air humidity at 35 °c | ≤95 % |