THERMOSTATIC CONTROL VALVE
DN32---thermostatic control valve
DN32-THERMOSTATIC CONTROL VALVE
Ideal working pressure | 0.1-0.5Mpa |
Cold water inlet temp. | 4-29 ℃ |
Hot water inlet temp. | 50-90 ℃ |
Mixed water outlet temp. | 35-45 ℃ customized |
Flow rate (1 bar pressure drop) | 66.67L/Min |
Temp accuracy | ±2℃ |
Body material | Stainless Steel Plated Nickel |
Thread | G 1-1/4″ Male Thread |
Standard | QB2806-2006 |
1.Technical Data
Model:DN32 Port size: G1-1/4”
a. Working pressure:0.03-1Mpa
b. Ideal working pressure:0.1-0.5Mpa
c. Maximum working temperature:≤99 ℃
d. Flow rate(1 bar pressure drop): 4Cb.m./H (Same as 66.67L/Min)
thermostatic control valve , thermostatic valve , control valve
Flow rate for pressure:
Knob Temperature :
Position | Min | 1 | 2 | 3 | 4 | 5 | 6 | 7 | Max |
Temperature(℃) | - | 30 | 33 | 35 | 37 | 39 | 42 | 45 | - |
thermostatic control valve , thermostatic valve , control valve
2. Materials of Construction
a. Valve body : brass plated nickel
b. Shutter : PPO
c. Spring : Stainless steel
d. Connection : Inlets-M, Outlet-M
thermostatic control valve , thermostatic valve , control valve
3. Features:
a. Fail-safe on Hot or Cold Supply Failure
b. Delivers Stable Mixed Water Temperature
c. Extended Mix Temperature Range : 35-45 C
d. Idea for Domestic Water Application
e. Tamper-Proof Cap
thermostatic control valve , thermostatic valve , control valve
4. Usage of TMVs
For wash hand basins, bidets, baths and showers in hospitals, schools, sport and leisure facilities, prisons and other public buildings.
thermostatic control valve , thermostatic valve , control valve
5. Installation Precaution:
a.All installations should be carried out by a Licensed Professional.
b.Install in accordance with markings on valve body. i.e. hot water inlet-marked H, cold water inlet-marked C
c. After temperature setting, if inlets temperature or pressure fluctuates, outlet temperature variation is within +/-2 C.
d.The external check valves at inlets prevent cross-flow of hot&cold water when inlets pressure is not the same.
e.If the ratio between two inlets is too large, one flow-limiting valve should be fixed at the side of higher pressure.
f. Prior to installation, provisions should be made to flush the piping of any debris or other foreign materials to ensure proper system operation