90Kw/113kva air-cooled Deutz engine generator silent type high quality (OEM manufacturer)
USD $2,000 - $10,000 /Set
Min.Order:1 Set
Fujian Haiweineng Electrical Machinery Co., Ltd.
90Kw/113kva air-cooled Deutz engine generator silent type high quality (OEM manufacturer)
Generator Data
Genset model | HDZF113(open type) | |||
HDZF113S (silent type) | ||||
Frequency | 50Hz/1500rpm, 60Hz/1800rpm | |||
Voltage | 110/220, 220/380, 230/400, 240/415, 254/440V | |||
Rated power | 90Kw/113kva | |||
Standby power | 99Kw/125Kva | |||
Phase | 3 Phase or 1 Phase | |||
Fuel tank capacity | 8-12 hours fuel tank | |||
Fuel consumption | 20.7L/H | |||
Silent level | 60dB-85dB at 7m |
Engine Data
Engine | Deutz F8L413F | ||
Aspiration | NA | ||
Type | 4-Stroke, In Line | ||
Frequency /speed | 50Hz/1500rpm, 60Hz/1800rpm | ||
Rated power | 90kw/121hp | ||
Cylinder | 8 | ||
Displacement | 12.763L | ||
Bore*Stroke | 125mm*130mm | ||
Governing system | Mechanical and Electric | ||
Start system | Electric start | ||
Cooling way | Air-cooled |
Alternator
Alternator | HWN-274C | ||
Frequency/Speed | 50Hz/1500rpm,60Hz/1800rpm | ||
Rated power | 90Kw/113kva | ||
Standby power | 99Kw/125Kva | ||
Phase | 3 phase or 1 phase | ||
Protection class | IP21 or 23 | ||
Excitation | Brushless, self-excitation | ||
Altitude condition | <1000m | ||
Insulation class | H | ||
Tel.Influence Factor | <50 | ||
Tel.Harmonic Factor | <2% | ||
Efficiency | 93.80% | ||
Cooling Air Flow | 1.035m3/s | ||
Power Factor | 0.8 |
Control Panel:
The G601A is an aoto control and protection module of generator.
The control modes of manual or auto are selectable by buttons on
panel. Manual starts or stops Genset under manual mode by button on
panel. Auto starts or stops Genset under auto Mode by remote switch
input signal. The modules is adopted LCD, which displays running status
and operating parameters of generator.
a. Generator Indicator 1. Stop/Reset/Value Decend
B. Voltage Change-Over Switch 2. Auto button/LED
c, Voltge Meter 3. Manual Start Button/LED
d. Engine Control Moduel 4. Start Button
e. Current Meter 5. Enter into Submenu/Menu
f. Current Change-Over Switch 6. Failure LED
g. Key Switch
Generator Protection:
&Generator Warning:
1. Fail to charge 2.Battery Low/High voltage 3.Low oil pressure
4. High Temperature 5. High/Low voltage 6.Over speed/ Under speed
7. Auxiliary Warning
When warns occure, the status indicator light flash. but failure will not be
locked and the unit will not shut down, once fail removed warning indicator
auto turn off.
& Generator Shutdown Alarm:
1. Fail to start 2. Fail to stop 3.Emergency stop
4. Low oil pressure 3. High temperature 4. Over speed
5. Auxiliary Failure
Shutdown failures immediately lock system and stop generator, it only can
operate controller agian after removing failures and press rest button to unlock.
Control Panel (AMF for option)
There are many international brand generator controller for our cusomer 's choice,
such as Smartgen, Deep sea, Compny, Harson and so on.
ATS (Automatic transfer switch for option)
Upon detection of a mains(utility) failure the module automatically starts the
generator set, once the mails (utility) power has been restored it instructs the
generator set to stop
Mobile for option
Two wheels: Four wheels:
Standard parts:
Starting Battery | Battery Charger | Battery Wire | Flexible Pipe |
Cooling Radiator | Float Battery Charger | Control System | Base Frame |
Flang | Wire diagram | Manual Book |
Option Accessories
ATS | External Fuel Tank | Silent Canopy |
Synchronization Panel | Automatic Fuel Tank | Weatherproof Canopy |
ABB Breaker | Oil Drain Pump | Mobile trial |
PMG | Water Preheater |
Aytu-condensation heater | Lub Oil Preheater |
Paralles droop | Spare parts |