Copper Tape Wraping Shield PVC Insulated Nuclear Power Plant Cable
USD $0.3 - $35.3 /Meter
Min.Order:500 Meters
Hengyang Hengfei Cable Co., Ltd.
This product is used as 1E-class circuit for the power configuration, control, testing, communications and instrument
compensation of nuclear island factory building of nuclear power plant.
Construction
Conductor copper
Product description
a,Rated voltage(U0/U):0.6/1KV.
b,Max. permissible continuous operating temperature of conductor is 90°C, while for short circuit (no more than four seconds) the temperature is 250°C.
c,The ambient temperature under installation is -10°C~40°C.
d,The permissible bending radius under installation:
For Unshielded Cable: no less than 6 times of overall diameter
For shielded cable: no less than 8 times of overall diameter
e,Min. permissible ambient temperature under installation: -40°C
f,Normal useful life: 50 years.
g,Special properties of cable:
(1)The cable can undergo bundled burning test specified in GB/T18380.3 (IEC 332-3).
(2)The insulated conductor of cable can undergo vertical burning test specified in GB/T18380.1 (IEC332-1).
(3)The low smoke property of cable conforms to the regulations specified in GB/T 17651(IEC61034): light transmittance ≥60.
(4)The low halogen property of cable conforms to regulations specified in GB/T 17650.2(IEC60754-2): PH≥4.3,electrical conductivity<10μs/mm.
h,Electric property of cable:
(1)Cable can withstand the test of AC 3500V/5min without breakdown;
(2)The resistivity of conductorρ20 not more than 0.0172410Ω·mm²/m
(3)Insulation resistance constant: K20 not less than 3670MΩ·km,K60 not less than 367 MΩ·km,K90 not less than 36 MΩ·km.
About us