600KVA Diesel Geneset
Negotiable /Set
Min.Order:3 Sets
Fuan Wangwantong Electric Machinery Co., Ltd.
600KVA Diesel Genset
1. Engine
We selects engine model " P222LE" from Doosan Infracore Co., Ltd.
2. Alternator
coupled with our WT series A.C. synchronous brushless alternator
3. Gensets’ electric performance
Gensets compliance with all main standards, such as: GB/T2820, ISO8528, IEC34, VDE0875-N
Prime output power: 480KW/600KVA
Rated voltage: 400/230V
Phase/connecting method: 3 phase 4wire/Y type connection
Rated frequency: 50/60hz
Rated speed: 1500/1800rpm
Excited type: Brushless, self excited or PMG
Insulation: Class H
Protection: IP22
Voltage regulation: AVR automatic control
Altitude above sea level: ≤1000 meters
Ambient air temperature: ≤40°C
Relative air humidity: ≤ 90%
Controller system
1.Standard control panel, including voltmeter, frequency meter, ampere meter, water temperature gauge, oil temperature gauge, oil pressure gauge, AMF control module, oil level indicator, emergency button, preheating button, battery voltage gauge, hours running counter for protection and transfer.
2. It can be with ATS electric control cabinet, including circuit breaker, LCD or LED auto controller, indicating lamp, transfer switch, etc.. Automatic transfer switch (ATS) uses update technology, which can be automatic control for on-off electricity, remote monitoring, automatic parallel operation, etc.
Technical Data
Gensets | Gensets Model | WT2-DS660 | ||
Prime power(KW/KVA)(three phase) | 480KW/600KVA | |||
Stand-by power (KW)(three phase) | 528KW/660KVA | |||
Automatic control panel | with ATS | |||
Engine | Engine Model | P222LE (V12) Doosan | ||
Prime power(KW) | 532KW | |||
Stand-by power (KW) | 574KW | |||
Air Intake System | Turbocharged, water cooling | |||
Cylinder*Bore*Stroke (Qty*mm*mm) | 12*128*142 | |||
Compression Ratio | 15:1 | |||
Alternator | Rating Voltage(V) | 3 phase, 400/230V | ||
Model | WANTONG | WT-C5E | ||
Rating Power(KW/KVA) | 480KW/600KVA | |||
Rating Frequency/speed | 50HZ/1500rpm | |||
Rating Power Factor | 0.8 lagging | |||
Steady voltage regulation | less than ±1.0% | |||
Phase/Connection | 3 phase, 4 wire/Y type connection | |||
Excited type/Voltage regulation | Brushless, self excited AVR automatic control | |||
Protection | IP22 | |||
Insulation | Class H |