HP6000 is specifically designed for operation in poor power areas. They provides high power density with long backup time in compact size. It’s ideal for ATMs, banking and other business critical applications. Users also can adjust charging current from 1A to 6A according to different applications.
Main Features:
True double-conversion
Microprocessor control optimizes reliability
Output power factor 0.8
Wide input voltage (110 V – 300 V)
Converter mode available
ECO mode for energy saving (Only available for 1-3KVA)
Generator compatible
Smart SNMP works well with either USB or RS-232 together
Comprehensive display allows easy monitoring and access of UPS status
Input power factor correction
Adjustable battery number only available for 6K and up models
Optional isolation transformer available
Technical Specifications:
Model | HP1058 5K (L) | HP1066 6K (L) | HP1100 10K (L) | ||
PHASE | Single phase with ground | ||||
CAPACITY | 5000VA / 4000W | 6000VA / 4800W | 10000 VA / 8000 W | ||
INPUT | |||||
Nominal Voltage | 208/220/230/240VAC | ||||
Input Voltage Range | 110-300 VAC (Based on load at 50%) | ||||
176-300 VAC (Based on load at 100%) | |||||
Frequency Range | 46~54 Hz or 56~64 Hz | ||||
Power Factor | more than 0.99 @ Nominall Voltage (100% load) | ||||
OUTPUT | |||||
Output Voltage | 208/220/230/240VAC | ||||
Voltage Requlation | +/-1 % | ||||
Frequency Range (Synchronized Range) | 46~54 Hz or 56~64 Hz | ||||
Frequency Range (Batt. Mode) | 50 Hz or 60Hz +/- 0.1 Hz | ||||
Current Crest Ratio | 3:01 | ||||
Harmonic Distortion | less than 3 % THD (Linear Load) | ||||
less than 5 % THD (Non-linear Load) | |||||
Transfer Time | AC to DC | Zero | |||
Inverter to Bypass | Zero | ||||
Waveform (Batt. Mode) | Pure Sinewave | ||||
EFFICIENCY | |||||
To AC Mode | 89% | 92% | 93% | ||
To Battery Mode | 88% | 90% | 91% | ||
BATTERY | |||||
Standard Model | Battery Type | 12 V / 9 Ah | 12 V / 9 Ah | 12 V / 9 Ah | |
Numbers | 8 | 16 | 16 | 20 | |
Typical Recharge Time | 4 hours recover to 90% capacity | 9 hours recover to 90% capacity | |||
Charging Current (Max.) | 1.0 A | 1 A / 2 A | |||
Charging Voltage | 115.2 VDC +/-1% | 218.4 VDC +/-1% | 218.4 VDC +/-1% | 273VDC +/-1% | |
Long-run Model | Battery Type | Depending on the capacity of external batteries | |||
Numbers | 8 | 16 | 16 | 20 | |
Charging Current (Max.) | 1A/2A/4A/6A (Adjustable) | 1A/2A/4Adjustable) | |||
Charging Voltage | 115.2 VDC+/-1% | 218.4 VDC +/-1% | 218.4 VDC +/-1% | 273VDC +/-1% | |
INDICATORS | |||||
LCD Display | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators | ||||
ALARM | |||||
Battery Mode | Sounding every 4 seconds | ||||
Low Battery | Sounding every second | ||||
Overload | Sounding twice every second | ||||
Fault | Continously sounding | ||||
PHYSICAL | |||||
Standard | Dimension, D*W*H (mm) | 442 * 190 * 688 | 369 * 190 * 688 | 442 * 190 * 688 | |
Model | Net Weight (kgs) | 43 | 61 | 66 | 75 |
Long-run Model | Dimension, D*W*H (mm) | 442 * 190 * 318 | 369 * 190 * 318 | 442 * 190 * 318 | |
Net Weight (kgs) | 15 | 12 | 16 | 18 | |
ENVIRONMENT | |||||
Humidity | 0-95% RH @ 0-40°C | 0-95% RH @ 0-50°C | 0-95% RH @ 0-40°C | ||
(non-condensing) | (non-condensing) | (non-condensing) | |||
Noise Level | Less than 58dBA@ 1 Meter | Less than 55dBA@ 1 Meter | Less than 58dBA@ 1 Meter | ||
MANAGEMENT | |||||
Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and MAC | ||||
Optional SNMP | Power management from SNMP manager and web browser | ||||
6-10KVA: Derate to 60% of capacity in Frequency converter mode and to 90% when the output voltage is adjusted to 208VAC | |||||