stationary battery tester
Negotiable /Unit
Min.Order:1 Unit
Xi'an Foresight Electronics Technology Co., Ltd.
General:
110V Battery Load Bank is specifically designed for the maintenance of the lead-acid battery discharge in the electricity sector. It is a new high-tech intelligent product that provides safe, reliable and convenient constant testing equipment for the DC system
Product Type:
Different discharge current range
String Voltage | 110VDC |
Discharge current Range | 30A 60A 100A 150A 200A 300A |
Factory Inspection:
Main Functions and Features:
1,Used to discharge to battery string removed from the system
2,Discharge to Battery string voltage as 120V, Cell voltage as 1.2V/2V/6V/12V
3,4 adjustable stop points and multiple alarm designs to control the discharge process intelligently
4,7inch LCD touch screen for easy operation and showing various parameters real time
5,Support RS232real time monitoring by PC or SD Carddownload data after discharge
6,PC software for capacity evaluation and report generation
7,Optional wireless modules for 1.2V/2V/6V/12V cells voltage real-time measuring
1,On-line monitoring test setting interface:
Online monitoring for battery string: when the battery pack is under the state of online discharge, uniform charge and floating charge, perform real-time online monitoring for all cells. The monitoring includes string voltage, cell voltage, charge/discharge current, monitoring time of battery string, charge/discharge capacity of battery string and etc.
Discharge test setting interface
Perform discharge of constant current taking advantage of intellectualized dummy load after the battery pack is removed from system, set up the parameters of “discharge current”,“discharge time ”,“discharge capacity” ,“final protective voltage of whole pack” and“ final protective voltage of cell”, and the tester could carry out discharge function automatically, display discharge current,battery discharged capacity,the whole pack voltage, cell voltage, discharge time and etc at real time;
Multiple Adjustable Stop Points
FST-CT offers 4 adjustable points for test stop points to avoid excessive discharge:
Stop Point | Setting Range |
String Low Voltage | 0 - 135.0 V |
Discharge Time | 0 - 99 Hour 99 Min |
Discharge Capacity | 0 - 3000 AH |
Cell Low Voltage | 0 - 15.00 V |
1,The instruments can analyze according to main test function on the histogram and the curve chart. It’s unnecessary to upload the result in PC.
Providing data management, print, analyze, count report, automatic generate test report. Amplify or minify the voltage curve for easy observation
Features | Specifications | ||||||
Model | 110/60 | 110/100 | 110/150 | 110/300 | |||
String Voltage measurement range | 0~135V | ||||||
String Voltage Resolution | 0.01V | ||||||
Voltage measurement accuracy | ≤±0.5% | ||||||
Cell Voltage Resolution | 0.01V | ||||||
Discharge current Range | 2~60A | 2~100A | 2~150A | 2-300A | |||
80~135V | |||||||
Current Measurement Resolutions | 0.1A | ||||||
Cell voltage measurement type | 1.2V/2V: 0-4V; 6V:0-8V; 12V: 0-15V | ||||||
Power Supply | 220VAC±15% 50Hz/60Hz | ||||||
Cooling mode | Air Cooling | ||||||
Communication Mode | USB Communication port and SD Card storage | ||||||
Display | 7inch Touch screen | ||||||
High-Voltage insulation test | Input-The enclosure:2200Vdc 1min Input-Output:2200Vdc 1min Output- The enclosure:700Vdc 1min | ||||||
Safety standard | EN610950 | ||||||
CE Certificate | LVD: EN61010-12010; EMC:EN61326-1:2013 | ||||||
Work Temperature | -5~50℃ | ||||||
Storage Temperature | -40~70℃ | ||||||
Humidity | Relative humidity 0~90%(40±2℃) | ||||||
Noise | <60dB | ||||||
Dimensions | 480x225x410mm | 600x250x410mm | 600x225×x630mm | 1050x850x300 | |||
Weight | <13Kg | <15.5Kg | <25Kg | <50Kg |
Goods Shelf:
Workshop:
SHIPPING SERVICE: