AC Dummy load
Negotiable /Set
Min.Order:1 Set
Xi'an Foresight Electronics Technology Co., Ltd.
Function Feature
l Steady-state test: automatically detect 3-phase voltage, current, active power, inactive power, apparent power, power factor, frequency, run time, total energy and so on.
l Transient-state test: according the presetted power values, IAC-380 series can create a loading dips and drops, automatically detect the maximum and minimum values of each phase voltage, current and frequency in the dips and drops, and calculate the power & power factor in each phase.
l Setting test: according the presetted values, IAC-380 series can increase the load in steps by proportion up to the maximum power, and then decrease the load in steps. In this process, IAC-380 series will automatically detect the maximum and minimum values of voltage, current and frequency, 3-phase power & power factor in each steps.
l Fluctuation test: according the preset values, IAC-380 series can increase the load in steps by proportion up to the maximum power, and automatically detect the maximum and minimum values of voltage, current and frequency, 3-phase power & power factor.
l Harmonics analysis: IAC-380 series can analyze the current, voltage 2-20 THD (total harmonic distortion) in each phases.
l IAC-380 series can support both 3-phase and 1-phase power test. The most powerful unit can provide 100KW.
l Parallel operation: for the requirement of some high power test, IAC-380 series can co-work in parallel perfectly.
l Phase sequence test: automatically detect the phase sequence of the generator & UPS.
l Adopting 5.7 inch colorful touching LCD: English interface make the operation convenient and direct viewing.
l Without PC and other recording device, the internal data storage memory of IAC-380 series can save 250 groups of data
l The user can choose browsing the real-time data in the process of testing by the software shown by laptop screen, or download the data to PC by RS-485 or USB after the testing.
l Applying overheating precaution function, IAC-380 series can cut off the load, terminate the discharge and alarm the user automatically when overheating happen.
l IAC-380 series provide the emergent stop switch, the users can terminate the test manually by single button.
l Short circuit protection function, guarantee the test safe and stable.
Type: | IAC-380-50KVA
| IAC-380-100KVA
| |
Loading Power (constant adjustable) | 0~50KVA | 0~100KVA | |
Power Factor | Test range: 0.001~1.000 Resolution: 0.001 Accuracy: 0.5% | ||
Harmonics(THD) | Test range: 2~50 harmonics(THD) Resolution: 0.01% Accuracy: 1% | ||
Voltage | Test range: AC 0~450V Resolution: 0.1V Accuracy: 0.5% | ||
Frequency | Test range: 45~65 Hz Resolution: 0.01Hz Accuracy: 0.2% | ||
Current Display | Resolution: 0.1A,Accuracy: 0.5% | ||
Input Voltage | AC 3 Phase 380V / AC 1 Phase 220V | ||
Discharging Time | 0~99 hours 59 minutes, constant adjustable | ||
Cooling Mode | Air cooling
| ||
PC Communication | RS485, USB data port, USB disk port | ||
Internal Memory | Internal storage device can save 250 groups of data, and support download data by PC or USB disk | ||
Display Mode | 5.7 inch colorful touching LCD, English operating menu | ||
Display Items | 3 Phase voltage, current, frequency, temperature, power, total energy, run time | ||
Analysis | Software English version analysis PC software | ||
Power Source | 220V±10% or Power from the tested devices | ||
Dimension(mm) | 650*220*370 | 660×600×900 |