Multi-door Access Controller (4/8 doors)
Negotiable
Min.Order:1
Product Description
•The PC-1074 is designed for high-security access control and real-time monitoring environments from medium size to complex multi-site installations.
•It is an independent processing 4 doors access control package with metal enclosure, backup battery charger as an efficient space saving design.
•Suitable for applications with up to 64,000 users across a modular 1024 doors, allowing maximum flexibility for securing a growing enterprise. Each unit supports 8 Wiegands or RS-485 ports for entry & exit control.
•The system support Bar Code, Magnetic Stripe, Biometric and Smart Card Readers thru. Wiegand or ABA interface.
•Designed with 4 DI (digital input) and 4 DO (digital outputs) for light, air conditioning, surveillance, fire prevention or urgent rescuing system control.
Features
•Online Network with on board selectable RS-485/RS-232/RS-422(optional) and optional TCP/IP Ethernet.
•Up to 15,000 cards with 32,000 events. Optional 64,000 cards with 64,000 events.
•Multi technology of badges include proximity, smart card, biometric, hand free active card, mag. cards, etc.,
•8 wiegand readers for 4 doors. expandable to 16 wiegand readers for 8 doors. Optional 8 or 16 RS-485 readers for 8 doors by 2nd RS-485 port.
•4 digital inputs and 4 digital outputs with expansible 24/48/64 relays output for floors control.
•Global (4 or expandable 8 doors) or single doors APB without PC autonomous decision at local level without degradation and removable connectors
•Optional baud rate from 2,400 to 38,400 with optional encryption for communication security.
Specifications
•Metal Enclosure Dimensions: 273(L) x 218(W) x 80(H) mm
•Weight: 4.7kg ± 5%
•Power supply: DC 15V +10%, 1.7A
•Consumption current: 0.05 A (not include power requirement for lock & alarm)
•UPS: 7.2A/H
•Transmission rate: 9,600 bps, N,8,1
•Serial interface: RS-485, RS-232, RS-422(optional), TCP/IP(optional)
•Events: 32,000 standard, up to 64,000
•Card capacity: 15,000 standard, up to 64,000
•External reader: Wiegand 26, 34bits, RS-485 reader
•Time zone: 8 personal time zones, 8 time zones for auto operation mode
•Memory: 6 MB, EEPROM
•Operation temperature: 0°C ~ 50°C
•Humidity: 5%~95%
System configuration
We reserve the right to change the specification without prior notice or obligation!