1.1Preface
The Electric power supply power is the electric equipment developed with Resonant Soft switching Techniques.
Main characteristics
lWide range of input voltage
lHigh power density, forced air fan cooling, small size
lMultiple protections including phase loss protection, over current, over voltage, over temperature and short circuit.
lHigh stability of output voltage
lautomatic current sharing technique, parallel unequal current ratio<±5%.
1.2Main protection function of Module
1.2.1 Phase loss protection
Once phase loss, the module will shut down automatically for protection and send out warning signal.
1.2.2 Output overvoltage protection
To prevent the disastrous accident caused by outputting overvoltage, there is overvoltage protection circuit in the module. In case output overvoltage occurs, the module locks up automatically, the fault indication light is on, the faulty module quits work automatically and doesn’t affect the normal operation of the entire system. The overvoltage protection point is set at 34±1 VDC
1.2.3Output current limiting protect
The output current cannot increase infinitely. The maximum value of the output current of each module is limited to the rated output current, when voltage goes down to 12V, the output current value will start decrease to protect the equipment. The max output current value of the module can be continuously adjustable by adjust button. If the load output of the module, the module will play down the output voltage
1.2.4Output short-circuit protection
When output short circuit occurs, the module draws the output voltage to 0 immediately, limit the short circuit current below 15%limit current point to protect the module. The module will not be damaged under short circuit state for a long time, and can go back to work automatically after debugging. The Module also send out warning signal.
1.2.5Over-temperature protection
Over-temperature protection is mainly for protecting large power converters, under normal operating circumstance, the module design leaves enough margin, under special circumstance, when the module detects that the temperature of the radiator is over 90°C±5°C, it will shut down automatically to protect itself. When the temperature reduces below 80°C, the module will start up automatically.
1.2.6Insulation Strength
Input-Output :2000VAC Leakage current≤8mA
Input-Module Shell : 2000VAC Leakage current≤8mA
Output-Module Shell : 1000VDC Leakage current≤4mA
Result: No flashing or arcing within 1 minute
1.2.7 Insulation Resistance10MΩ
Test with 500V Megohm-meter, insulation resistance ≥50MΩ
1.2.8 Module parallel connection protection
There is parallel protection circuit in each module to ensure when the faulty module quits the system, the normal work of other modules and the system is not affected.
module project | TH24C80NZ | ||||
rated output current(A) | 80 | ||||
power(KW) | 2.4 | ||||
weight(kg) | 8 | ||||
cooling method | Fan cooling | ||||
Internal Radiator temperature | ≤30°C | ||||
Range of input Voltage(VAC) | min | 342 | |||
Rated | 380 | ||||
Max | 466 | ||||
Working Mode | Manual Operation | Floating Charge | Boost Charge | ||
rang of adjustable output voltage(VDC) | Min | 20 | 20 | 20 | |
Rated | 25 | 27 | 29 | ||
max | 30 | 30 | 30 | ||
Voltage Stabilization tolerance | ±0.5% | ||||
Voltage Stabilization tolerance | ±0.5% | ||||
Efficiency | ≥88% | ||||
Warning | Input phase loss, output over voltage, over temperature, short circuit | ||||
Indicate function: | Display of running, floating charge, boost charge and failure output code | ||||
Storage temperature(°C) | min | -30 | |||
Typical value | 25 | ||||
max | 60 | ||||
working temperature(°C) | min | -10 | |||
Typical value | 25 | ||||
max | 45 | ||||
Parallel unequal current ratio | ≤±3% | ||||
time delay of start-up(s) | 3~8 | ||||
Ripple Voltage(Ripple Coefficient) | ≤400mv(≤1%) | ||||
Grade of Load | Continuous working with Grade I(100%) rating output current | ||||
Stepless current limitation technology | The output current cannot increase infinitely. The maximum value of the output current of each module is limited to the rated output current | ||||
Output overvoltage protection function | After output overvoltage occurs(34±1VDC), the module locks up automatically to avoid the equipment being damaged | ||||
output short circuit protection | When output short circuit, the module protect itself automatically to avoid being damaged | ||||
Autonomous Floating charge/ Boost charge mode | When module is in manual operation mode, Floating charge and Boost charge will exchange automatically (in this conditions there is only working and failure indication) |