Substation Telecom 48/24V ac/dc power supply
USD $240 - $260 /Piece
Min.Order:1 Piece
Shijiazhuang Tonhe Electronics Technologies Co., Ltd.
Substation Telecom 48/24V ac/dc power supply
ac/dc power supply ac/dc power supply ac/dc power supply ac/dc power supply ac/dc power supply ac/dc power supply ac/dc power supply ac/dc power supply ac/dc power supply ac/dc power supply ac/dc power supply ac/dc power supply ac/dc power supply ac/dc power supply ac/dc power supply ac/dc power supply ac/dc power supply
Item | Set range | Default |
System set | ||
Charger quantity | 1~32 | 1 |
Sensor range | 100~3000A | 100A |
Charger set | ||
Float charge voltage | 43.0V~58.0V/21.0V~29.0V | 53.2V/26.6V |
Equalizing charge voltage | 43.0V~58.0V/21.0V~29.0V | 56.4V/28.2V |
Rated current | 10A, 20A, 25A, 30A, 50A, 100A | 20A |
Charger type | 48V/24V | 48V |
Alarm set | ||
AC over voltage | 380V~450V/220V-264V | 420V/264V |
AC under voltage | 300V~380V/176V-220V | 304V/176V |
Output over voltage | 43.0V~60.0V/20.0V~30.0V | 58.0V/29.0V |
Output under voltage | 43.0V~60.0V/20.0V~30.0V | 48.0V/24.0V |
Battery over voltage | 43.0V~60.0V/20.0V~30.0V | 58.0/29.0V |
Battery under voltage | 43.0V~60.0V/20.0V~30.0V | 48.0/24.0V |
Charging over current | 0~4000A | 400A |
LVDS backlash | 1.0V~10.0V | 5.0V |
Battery management | ||
Battery charge current limit | 1~3000A | 100A |
Float to equalizing charge current threshold | 0~3000A | 80A |
Equalizing to float charge current threshold | 0~3000A | 20A |
Tail current charge time | 0~9H | 3H |
Regular equalizing charge | YES/NO | YES |
Regular equalizing charge period | 0~999 days | 180 |
Temperature compensation centre | 15℃~35℃ | 25℃ |
Temperature compensation ratio | 0.00~0.5V/℃ | 0.03V/℃ |
Max equalizing time | 0~30H | 10H |
End of discharge voltage | 48.0~60.0V | 48.0 |
Max discharge time | 0~10H | 10H |
Communication set | ||
ADD | 1~30 | 1 |
Baud rate | 1200,2400,4800,9600 | 9600 |
Interface | RS485,RS232 | RS485 |
Password set | ||
Password set | 0~9999 | 0000 |