Transformer Oil Purifier (for 110 KV, 220KV, 300KV Transformer)
USD $5,000 - $8,000 /Set
Min.Order:1 Set
Chongqing Yuneng Oil-Filter Manufacturing Co., Ltd.
Transformer Oil Purifier Features Transformer Oil Purifier (for 110 KV, 220KV, 300KV Transformer)
1. Breakdown Voltage: ≥65KV
2. Water Content:≤5PPm
3. Gas Content: ≤0.2%
4. Precision of Filtration: ≤5μm
Item | Parameter | Type Unit | ZJB0.42KY | ZJB0.9KY | ZJB1.8KY | ZJB3KY | ZJB4.8KY | ZJB6KY | ZJB9KY | ZJB12KY | ZJB18KY |
| |||
Technical Parameter | Flow Rate | L/H | 420 | 900 | 1800 | 3000 | 4800 | 6000 | 9000 | 12000 | 18000 |
| |||
Limit vacuity | Pa | ≤20 | |||||||||||||
Working Vacuity | pa | ≤400 | |||||||||||||
Working Pressure | Mpa | ≤0.35 | |||||||||||||
Temperature Range | oC | 50-65 | |||||||||||||
Power Supply |
| 50Hz 380V 3-Phase 4-Wire (or as requested) | |||||||||||||
Total Power | KW | 3.6+0.75 | 9+1.5 | 12+1.5 | 30+3 | 2x24+3.3 | 2x30+4 | 3x30+6 | 4x30+7 | 5x30+9 |
| ||||
Inlet/Outlet Diameter | mm | 25/16 | 32/25 | 32/25 | 38/32 | 38/32 | 44/38 | 48/44 | 64/48 | 76/64 |
| ||||
Outer Size | Length | mm | 650 | 1100 | 1100 | 1500 | 1600 | 1650 | 1850 | 2100 | 2200 |
| |||
Width | mm | 500 | 850 | 900 | 1100 | 1200 | 1150 | 1250 | 1350 | 1400 |
| ||||
Height | mm | 900 | 1400 | 1400 | 1700 | 2100 | 2050 | 2150 | 2200 | 2300 |
| ||||
Weight | Kg | 60 | 120 | 200 | 500 | 600 | 800 | 1000 | 1500 | 2500 |
| ||||
Oil Treatment Index | Breakdown Voltage | KV | 60-65 | ||||||||||||
Water Content | ppm | 5-10 | |||||||||||||
Gas Content | % | ≤0.25 | |||||||||||||
Filtration Accuracy | µm | ≤3 |