Technical Parameters
Type JZ-0.6KY
capacity 10L/min (600L/h)
oil temperature -25°C ~70°C
working power 50Hz 380V 3 phase
total power 0.25 KW
inlet/outlet oil pipe 16/16 mm
size 70×30×120 cm
working noise≤78 dB(A)
weight 50Kg
working condition individual and continuous on line running.
After-treated oil Condition
Water content≤20PPm
Suspended particles ≤1~3μm
cleanness(NAS1638) ≤6 Grade
Function
Integrate the function of fineness filtration and dehydration..
it can effciently remove dissolved water, and control the water content,flash point and dielectrical strength.
it can efficiently remove particles in the oil, so that control the oil cleanness up to Nas6
Feature:
Stainless steel
Standard control box
Remote control system: filter element display of machine operation
Positive and negative direction control of the motor, protection of over-load of motor start and phase-lacking.
Humidity relay, 50%-100% adjustable.
Automatically run the filter equipment once after the operation of OLTC, start up the operation time can be set according to requirement from 0-99 hours, but it is usually set with 30 minutes. Another way is to filter every day at the fixed time lasting two hours. The two methods can be chosen accordingly.
Technical parameter list
project | dataname | Unit / type | JZ-0.6BF |
Technical parameter list | Flow | L/min | 10 |
Working pressure | Mpa | ≤0.5 | |
Power supply | KW | (380V-50HZ or as needed) | |
Total power | KW | 0.75 | |
Inlet(outlet )Diameter | DN | 25 | |
Outer size | mm | 530×350×1000 | |
weight | Kg | 100 | |
After filtration | Impurity size | μm | 1 |
cleanliness | NAS1638 | ≤6 |
Packaged by iran case or wood case or as needed, sent by LCL within 20 days after receive the payment.
How to maintain the oil purifier ?
A. check and adjust after oil purifier works for a period of time
1. all the electric control apparatus
2. temperature controller
3. oil seals and motor couplings
4. clean filter elements, check pumps and motors
5. all the pipes for leaking
B. Clean the motor and change the lubricating grease
C. Check and add specified lubricating oil to vacuum pump,
D. If oil purifier is not in use for one month or more, put it on a dry, flat ground, close all valves and electric cabinet, cove the whole machine with canvas.
We care about our customers' concern, work on help you to solve the problem on using the oil and provide you the best solution to guarantee your machine work well.