Din-rail bacnet power meter PMAC770-DR

Din-rail bacnet power meter PMAC770-DR

Negotiable /Piece

Min.Order:3 Pieces

Supply Ability:
10000 Piece / Pieces per Month
Port:
Zhuhai port
Payment Terms:
T/T Credit Card

Quick Details View All >

Place of Origin:
Guangdong, China
Brand Name:
Pilot
Model Number:
PMAC770-DR
Measuring Current Range:
0-50000A
Measuring Voltage Range:
0-690V
Accuracy Class:
0.5%

Zhuhai Pilot Technology Co., Ltd.

Business Type: Manufacturer,Trading Company
Zhuhai Guangdong China
Main Products: Power Meter ,Energy Meter ,Branch circuit power meter ,380V AC solar water pump controller ,Battery Monitoring system for Data Center

Product Details

Specifications

power meter
1. Real-time measurement, 0.5 Accuracy
2. Power quality analysis, Support online upgrade
3. CE KEMA

Din-rail bacnet power meter PMAC770-DR
Feature:
 
1. Multifunction RMS measurement
2. Demand calculation mode is programmable
3. Multi-tariff billing, historical data of 31 days and 12 months
4. Real-time measurement, Power quality analysis
5. Support online upgrade
6. Setpoint alarm
7. High accuracy, U, I up to 0.2% accurracy
8. Small size and 35mm DIN rail installation, Pluggable terminal, easy to install
9. LED indicates situation of the meter
10. RS485 Communication: Modbus-RTU protocol
11. Standard IEC62053-22/ 23, CE. KEMA
 
Basic function:
 
Real time metering
      Voltage (UL-L, UL-N, UL-L avg, UL-N avg)
      Current (3I, In, I avg)
      Power (3P, ∑P, 3Q, ∑Q, 3S, ∑S )
      Power factor (3PF, ∑PF )
      Energy (4 quadrant ±kWh and ±kvarh )
      Frequency (F)
      Demand & Max. demand (I, P, Q, S)
      Max./ min. value (U, I, P, Q)
      Multi-tariff energy
Power quality analysis
         Unbalance (U, I)
       Harmonic (31st )
       Harmonic RMS (0-31st )
       Harmonic energy (1st -13th )
       Voltage crest factor, current K factor, Load rate, Voltage deviation,
       Frequency deviation
Setpoint alarm
         Over/ under limit alarm
Record function
         SOE (event log), Real-time clock ( yyyy-mm-dd hh:mm:ss)
       Voltage/ frequency deviation, Voltage unbalance record
3DI + 2DO
         3 status input + 2 relay output
RS485--One Modbus-RTU protocol
 
 
Technical  specification:
 
Metering
True RMS, 1 sec refresh time
Input
 
 
Rate current: 1A or 5A
Rate voltage: direct 0 ~690V
Frequency: 50/ 60Hz
Overload
120% of rated, continuously
Instantaneous current: 10 times/ sec
Instantaneous voltage: 2 times/ sec
Status input
Wet contact, external power supply
Relay output
Node capacity: 250VAC/5A
Pulse output
Pulse constant: 1000~9999 programmable
Pulse width: 60~100ms programmable
Formula: 1 pulse = (1÷ pulse constant ×PT ×CT) kWh
Power frequency withstand voltage
AC 2KV/minute
Insulation resistance
≥50MΩ
Impulse withstand voltage
4kV (peak), 1.2/50uS
Power supply
85-265V AC   / 100-300V DC
Power loss
≤5VA
Communication
RS485 serial, support Modbus-RTU
Baud rate: 1200, 2400, 4800, 9600, 19200, 38400bps
Address: 1~247
Dimension
(L x W x H)
Panel: 96 x 96 x 13.5mm
Cut-out: 90 x 90 x 45.1mm
IP index
IP52 (front panel) and IP30 (case)
Weight
Basic unit: approx 400gr.
Environment
 
Operating temperature: -10°C~ +55 °C
Storage temperature: -40°C~ +70 °C
Humidity: 5%~95% non-condensing
 

 

 

 
 
 
Din-rail bacnet power meter PMAC770-DRDin-rail bacnet power meter PMAC770-DRDin-rail bacnet power meter PMAC770-DR
 
 
 
 

HUHAI PILOT TECHNOLOGY CO., LTD.
                        

Add: No. 15, Keji 6 Road, Chuangxin Haian, Tangjia Hi-tech Zone,
Zhuhai, Guangdong, China   
Post Code: 519085 Tel: +86 756 3629687/ 3629673         
Fax: +86 756 3629600/ 3629700          

Contact Supplier

Mr. Jackey Zhou Director Chat Now
Telephone
86-756-3629673,3629699
Mobile
008613928018523
Fax
86-756-3629600,3629700
Address
No.15, Keji 6 Road, Chuangxin Haian, Tangjia Hi-tech Zone, Zhuhai, Guangdong Zhuhai,Guangdong

You May Like

New Products

Recommended Products

View More View Less

Find Similar Products By Category

Measurement & Analysis Instruments > Electrical Instruments > Power Meters
Categories
Hi~