30W Industrial DIN-Rail Power Supply(switching power supply)
Negotiable /Piece
Min.Order:10 Pieces
Yueqing Ledisen Imp. & Exp. Co., Ltd.
30W Industrial DIN-Rail Power Supply(switching power supply)
Features:
Universal AC input/Full range
Protections: Short circuit/Over load/Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
LED indicator for power on
100% full load burn-in test
MODEL | DR-30-5 | DR-30-12 | DR-30-15 | DR-30-24 | |
---|---|---|---|---|---|
OUTPUT | DC VOLTAGE | 5V | 12V | 15V | 24V |
RATED CURRENT | 3A | 2A | 2A | 1.5A | |
CURRENT RANGE | 0 ~ 3A | 0 ~ 2A | 0 ~ 2A | 0 ~ 1.5A | |
RATED POWER | 15W | 24W | 30W | 36W | |
RIPPLE & NOISE (max.) Note.2 | 80mVp-p | 120mVp-p | 120mVp-p | 150mVp-p | |
VOLTAGE ADJ. RANGE | 4.75 ~ 5.5V | 10.8 ~ 13.2V | 13.5 ~ 16.5V | 21.6 ~ 26.4V | |
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | ±1.0% | |
LINE REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
LOAD REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
SETUP, RISE TIME | 100ms, 30ms/230VAC 100ms, 30ms/115VAC at full load | ||||
HOLD TIME(Typ.) | 100ms/230VAC 30ms/115VAC at full load | ||||
INPUT | VOLTAGE RANGE | 85 ~ 264VAC 120 ~ 370VDC | |||
FREQUENCY RANGE | 47 ~ 63Hz | ||||
EFFICIENCY (Typ.) | 74% | 81% | 82% | 83% | |
AC CURRENT | 0.88A/115VAC 0.48A/230VAC | ||||
INRUSH CURRENT(max.) | COLD START 15A/115VAC 30A/230VAC | ||||
PROTECTION | OVERLOAD | 105 ~ 160% rated output power | |||
Protection type: Constant current limiting,recovers automatically after fault condition is removed | |||||
OVER VOLTAGE | 5.75 ~ 6.75V | 13.8 ~ 16.2V | 17.25 ~ 20.25V | 27.6 ~ 32.4V | |
Protection type: Shut down o/p voltage,re-power on to recover | |||||
ENVIRONMENT | WORKING TEMP. | -20 ~ +60ºC (Refer to output load derating curve) | |||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | ||||
STORAGE TEMP., HUMIDITY | -20 ~ +85ºC, 10 ~ 95% RH | ||||
TEMP. COEFFICIENT | ±0.03%/ºC (0 ~ 50ºC) | ||||
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes | ||||
SAFETY & EMC (Note.4) | SAFETY STANDARDS | ||||
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | ||||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC | ||||
EMI CONDUCTION & RADIATION | Compliance to EN55022 (CISPR22) Class B | ||||
HARMONIC CURRENT | Compliance to EN61000-3-2,-3 | ||||
EMS IMMUNITY | Compliance to EN61000-4-2,3,4,5; ENV50204, EN55024, Light industry level, criteria A | ||||
OTHERS | MTBF | 441.5K hrs min. MIL-HDBK-217F (25ºC) | |||
DIMENSION | 78*93*56mm (L*W*H) | ||||
PACKING | 0.27Kg; 48pcs/14Kg/1.02CUFT | ||||
NOTE | 1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature. 2.Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3.Tolerance: includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |