Specifications
40W Industrial DIN-Rail Power Supply(switching power supply)Input:110~ 220VAC Full rangeOutput:5V,12V,24V,48V
40W Industrial DIN-Rail Power Supply(switching power supply)
Features:
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
LED indicator for power on
DC OK relay contact
No load power consumption<0.75W
100% full load burn-in test
MODEL | MDR-40-5 | MDR-40-12 | MDR-40-24 | MDR-40-48 | |
---|---|---|---|---|---|
OUTPUT | DC VOLTAGE | 5V | 12V | 24V | 48V |
RATED CURRENT | 6A | 3.33A | 1.7A | 0.83A | |
CURRENT RANGE | 0 ~ 6A | 0 ~ 3.33A | 0 ~ 1.7A | 0 ~ 0.83A | |
RATED POWER | 30W | 40W | 40.8W | 39.8W | |
RIPPLE & NOISE (max.) Note.2 | 80mVp-p | 120mVp-p | 150mVp-p | 200mVp-p | |
VOLTAGE ADJ. RANGE | 5 ~ 6V | 12 ~ 15V | 24 ~ 30V | 48 ~ 56V | |
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | ±1.0% | |
LINE REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
LOAD REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
SETUP, RISE TIME | 500ms, 30ms/230VAC 500ms, 30ms/115VAC at full load | ||||
HOLD TIME(Typ.) | 50ms/230VAC 20ms/115VAC at full load | ||||
INPUT | VOLTAGE RANGE | 85 ~ 264VAC 120 ~ 370VDC | |||
FREQUENCY RANGE | 47 ~ 63Hz | ||||
EFFICIENCY (Typ.) | 78% | 86% | 88% | 88% | |
AC CURRENT | 1.1A/115VAC 0.7A/230VAC | ||||
INRUSH CURRENT(max.) | COLD START 30A/115VAC 60A/230VAC | ||||
PROTECTION | OVERLOAD | 105 ~ 150% rated output power | |||
Protection type: Constant current limiting,recovers automatically after fault condition is removed | |||||
OVER VOLTAGE | 6.25 ~ 7.25V | 15.6 ~ 18V | 31.2 ~ 36V | 57.6 ~ 64.8V | |
Protection type: Shut down o/p voltage,re-power on to recover | |||||
FUNCTION | DC OK ACTIVE SIGNAL (max.) | Relay contact rating(max.): 30V/1A resistive | |||
ENVIRONMENT | WORKING TEMP. | -20 ~ +70ºC (Refer to output load derating curve) | |||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | ||||
STORAGE TEMP., HUMIDITY | -40 ~ +85ºC, 10 ~ 95% RH | ||||
TEMP. COEFFICIENT | ±0.03%/ºC (0 ~ 50ºC) | ||||
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes | ||||
SAFETY & EMC (Note.4) | SAFETY STANDARDS | Design refer to UL508, TUV EN60950-1 | |||
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | ||||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC | ||||
EMI CONDUCTION & RADIATION | Compliance to EN55022 (CISPR22) Class B | ||||
HARMONIC CURRENT | Compliance to EN61000-3-2,-3 | ||||
EMS IMMUNITY | Compliance to EN61000-4-2,3,4,5; ENV50204, EN55024, Light industry level, criteria A | ||||
OTHERS | MTBF | 301.7K hrs min. MIL-HDBK-217F (25ºC ) | |||
DIMENSION | 40*90*100mm (W*H*D) | ||||
PACKING | 0.3Kg; 42pcs/13.6Kg/0.82CUFT | ||||
NOTE | 1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature. 2.Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3.Tolerance: includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5.Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time. |