NW24 Environment Monitoring Controller for Telecommunication
USD $1 - $100 /Set
Min.Order:10 Sets
Hangzhou Xinjian Electronic Co., Ltd.
NW24 Environment Monitoring Controller for Telecommunication is an economic solution for telecom shelter's remote monitoring management.
It can control the work of two air conditioners as well as the centrifugal fan based on the detected temperature by sensors.
Fire/smog, intruson, water leakage, motion, battery voltage, fan failure can also be monitored.
Real-time records temp, alarm code and work status, upload date via Mini USB port.
Output DC 0 to 10V PWM dry contact signal to centrifugal fan.
Output on/off switch signal to air conditioners.
Alarm signal output.
Function: | |
Program | every work temp. can be programmed |
Display | LED display temperature, and alarm code |
Auto control | control the work of two air-conditioners and EC fan based on indoor, outdoor temperature. |
Manual control | Air-conditioner and EC fan can be controlled by manual |
Fan speed control | Fan speed can be adjusted ( half speed to full speed) The EC fans works only the environment satisfies following conditions: 1. no fire alarm 2. outdoor temperature > indoor temperature, and the difference >t09. |
Logging | can real-time logging one moth date, interval 15 minutes. |
Monitor | two temperature, fire, EC fan failure, AC power off. |
Alarm | 1 relay output alarm signal |
Communication | supply monitor software (installed in PC), upload alarm date via Mini USB port. |
Technical parameter: | |
Input voltage | DC 48V |
Display | LED display temp., alarm code, parameter code and value Indicate light display work status and alarm |
Work ambient temperature | -25°C~+55°C |
Work ambient humidity | 5%~95%RH |
Temperature detect | 2 x NTC 103AT, detect range: -40°C ~ 70°C accuracy: ± 1°C compensation value can be programmed |
Alarm output relay | 1 pcs |
Control signal for air-conditioner | Switch signal |
Control signal for EC fan | DC 0-10V |
Memory capacity | 3000pcs |
Alarm
Code | Definition | Phenomena |
E01 | High temp. | Indoor temp. ≥ t08 |
E03 | Smog fire alarm (option) | There is a smog fire in shelter |
E05 | AC power off | AC power failure |
E09 | EC fan fault | Feedback frequency signal of fan < F-E |
E12 | Temp. sensor failure | Short or open circuit of temp. sensor |
E18 | Air-con. has cooling efficiency fault | Indoor temp also raise when air-con work after A01 time |